Chapter 3: Configuration and commissioning
1X-X3E Series Installation Manual
51
3. Press Enter
4. Save your changes.
The available settings for this feature are shown below.
Display
Description
Setting the number of minutes (range is from 0 to 5).
Setting the number of seconds (range is from 0 to 55).
Actuator delay for start manual call point
Use this menu to configure the control panel behaviour after a manual
extinguishing event (from the MCP Start point): activate the actuator immediately
or apply the actuator delay configured for automatic extinguishing events.
The default settings are:
• Basic standard mode = On
• Basic evacuation mode = Off
To configure the actuator delay for start manual call point:
1. Set the display as shown below, and then press Enter.
The red Start MCP LED flashes fast to indicate that the configuration menu is
active.
2. Select a value using the value selection buttons (2 and 4).
3. Press Enter
4. Save your changes.
The available settings for this feature are shown below.
Display
Description
Actuator delay applies to the MCP Start.
MCP Start activates the actuator immediately (no delay).