Chapter 3: Configuration and commissioning
1X-X3E Series Installation Manual
41
Display
Menu
Values
Fault latch
ON/OFF
Default: On
Module number
00 to 04
See “Expansion board function” on
page 63.
Firenet identifier
0 to 32
0: Stand-alone (no networking)
Default: 0
Firenet group. Allows you to configure
the panel to work in a 32-node network
or in a group of 32 nodes inside a 250-
node network (0000-0250)
0000 to 0218
Default: 0000
The number has four digits. Identified
by position, these are: 1234.
Press Up to enter the first two digits of
the number (positions 1 and 2).
Press Down to enter the last two digits
of the number (positions 3 and 4).
Firenet analogue remote node
0000 to 0250
Default: 0000
The number has four digits. Identified
by position, these are: 1234.
Press Up to enter the first two digits of
the number (positions 1 and 2).
Press Down to enter the last two digits
of the number (positions 3 and 4).
Firenet number of nodes [1]
2 to 32
Default: 2
Firenet initial zone number
0001 to 9999
Default: 0001
The number has four digits. Identified
by position, these are: 1234.
Press Up to enter the first two digits of
the number (positions 1 and 2).
Press Down to enter the last two digits
of the number (positions 3 and 4).
Firenet global controls
ON/OFF
Default: On
Firenet loop class
A/ B
Default: B
Process remote zones
ON/OFF
Default: On
Firenet map
01 to 32
ON/OFF
On for nodes 1 and 2, Off for the rest
Firenet repeater map
01 to 32
ON/OFF
On for nodes 1 and 2, Off for the rest
Summary of Contents for 1 3E Series
Page 1: ...1X X3E Series Installation Manual P N 501 419303 1 20 ISS 20JUL21 ...
Page 86: ...Chapter 4 Maintenance 80 1X X3E Series Installation Manual ...
Page 106: ...Appendix A Configuration presets 100 1X X3E Series Installation Manual ...
Page 110: ...Appendix B Regulatory information 104 1X X3E Series Installation Manual ...
Page 113: ......
Page 114: ......