Chapter 3: Configuration and commissioning
1X-X3E Series Installation Manual
49
Manual key mode
Use this menu to configure the manual key functionality if your control panel has
a key switch installed in the door. The default setting is off.
To configure the
manual
key mode:
1. Set the display as shown below, and then press Enter.
2. Select a value using the value selection buttons (2 and 4).
3. Press Enter.
4. Save your changes.
The available settings for this feature are shown below.
Display
Description
Manual-automatic and manual-only mode.
With this setting, the key functionality is as follows:
• If the key is turned to ON, the panel is set to Manual
mode
• If the key is turned to OFF, the panel is set to
Automatic mode
Access level functionality (default).
With this setting, the key functionality is as follows:
• If the key is turned to ON, operator level is active
• If the key is turned to OFF, public level is active
Note
If the manual key mode setting is On, the key takes priority over the keypad and
network related commands:
• If the key position is On (that is, the key is inserted and turned) the panel will
stay in manual mode independently of the operator level auto/manual button
actions on the keypad and related network commands.
• If the key position is OFF (that is, the key is not inserted or is inserted but not
turned) the panel accepts an operator level request to change the
auto/manual using the button or the related network commands.
Summary of Contents for 1 3E Series
Page 1: ...1X X3E Series Installation Manual P N 501 419303 1 20 ISS 20JUL21 ...
Page 86: ...Chapter 4 Maintenance 80 1X X3E Series Installation Manual ...
Page 106: ...Appendix A Configuration presets 100 1X X3E Series Installation Manual ...
Page 110: ...Appendix B Regulatory information 104 1X X3E Series Installation Manual ...
Page 113: ......
Page 114: ......