Actuator delay
When the control panel enters the extinguishing activation state, the actuator
delay starts counting down. The extinguishing actuator output is activated when
the delay time expires. (Activation of the MCP Hold or MCP Abort point prevents
the panel from entering the extinguishing activation state.)
Use this menu to configure an actuator delay of up to 60 seconds (in steps of 5
seconds). The default setting is for a 10-second delay.
To configure an actuator delay:
1. Set the display as shown below, and then press Enter.
The red Release LED flashes fast to indicate that the delay configuration
menu is active.
2. Select a delay value from 00 to 60 seconds using the value selection buttons
(2 and 4).
3. Press Enter.
4. Save your changes.
Reset disabled delay
When the control panel enters extinguishing activation, the reset disabled delay
starts counting down, and the reset is disabled until the delay expires.
Use this menu to configure a reset disabled delay of up to 30 minutes (in steps of
1 minute). The default setting is for a 2-minute delay.
To configure a reset disabled delay:
1. Set the display as shown below, and then press Enter.
2. Select a delay value from 00 to 30 minutes using the value selection buttons
(2 and 4).
3. Press Enter.
4. Save your changes.
Summary of Contents for 1 3E Series
Page 1: ...1X X3E Series Installation Manual P N 501 419303 1 20 ISS 20JUL21 ...
Page 86: ...Chapter 4 Maintenance 80 1X X3E Series Installation Manual ...
Page 106: ...Appendix A Configuration presets 100 1X X3E Series Installation Manual ...
Page 110: ...Appendix B Regulatory information 104 1X X3E Series Installation Manual ...
Page 113: ......
Page 114: ......