Chapter 3: Configuration and commissioning
1X-X3E Series Installation Manual
55
Battery fault check
Use this menu to configure the battery fault check, on or off. This determines
whether the battery fault is supervised or not. The default setting is On.
Note:
If disabled, it does not comply with EN 54-2 and EN 54-4.
To configure the battery fault check:
1. Set the display as shown below, and then press Enter.
The power supply fault LED flashes fast to indicate that the battery fault check
menu is active.
2. Select a value using the value selection buttons (2 and 4).
3. Press Enter.
4. Save your change
The available settings for this feature are shown below.
Display
Description
The battery fault check is enabled.
The battery fault check is disabled.
Earth fault check
Use this menu to configure the earth fault check, on or off. This determines
whether the earth fault is supervised or not. The default setting is On.
Note:
If disabled, it does not comply with EN 54-2 and EN 54-4.
To configure the earth fault check:
1. Set the display as shown below, and then press Enter.
The earth fault LED flashes fast to indicate that the battery fault check menu
is active.
2. Select a value using the value selection buttons (2 and 4).
3. Press Enter.
4. Save your change
Summary of Contents for 1 3E Series
Page 1: ...1X X3E Series Installation Manual P N 501 419303 1 20 ISS 20JUL21 ...
Page 86: ...Chapter 4 Maintenance 80 1X X3E Series Installation Manual ...
Page 106: ...Appendix A Configuration presets 100 1X X3E Series Installation Manual ...
Page 110: ...Appendix B Regulatory information 104 1X X3E Series Installation Manual ...
Page 113: ......
Page 114: ......