Chapter 3: Configuration and commissioning
50
1X-X3E Series Installation Manual
Enable flooding time
Use this menu to enable the control of the flooding time. The flooding time is the
time that the actuator remained activated (5 to 300 seconds in steps of 5
seconds). The default setting is off.
To enable the flooding time:
1. Set the display as shown below, and then press Enter.
The red Released LED flashes fast to indicate that the configuration menu is
active.
2. Select a value using the value selection buttons (2 and 4).
3. Press Enter
4. Save your changes.
The available settings for this feature are shown below.
Display
Description
Flooding time is enabled.
Flooding time is disabled.
Flooding time
Use this menu to set the flooding time for the actuator (5 to 300 seconds in steps
of 5 seconds). When the actuator is activated, the flooding time delay starts to
run. When the flooding time expires, the actuator output is deactivated.
The default value is 0 min, 0 sec.
The maximum value is 5 min.
If the flooding time is set to 0 min, 0sec., the ‘flooding time enable’ will be set to
OFF.
To configure the flooding time:
1. Set the display as shown below, and then press Enter.
The red Released LED flashes fast to indicate that the configuration menu is
active and nn (minutes) and SS (seconds) appears.
2. Select a value using the value selection buttons (2 and 4).
Summary of Contents for 1 3E Series
Page 1: ...1X X3E Series Installation Manual P N 501 419303 1 20 ISS 20JUL21 ...
Page 86: ...Chapter 4 Maintenance 80 1X X3E Series Installation Manual ...
Page 106: ...Appendix A Configuration presets 100 1X X3E Series Installation Manual ...
Page 110: ...Appendix B Regulatory information 104 1X X3E Series Installation Manual ...
Page 113: ......
Page 114: ......