Chapter 3: Configuration and commissioning
1X-X3E Series Installation Manual
67
Therefore, change this setting if you want to keep activations and indications
independent in different control panels. Example: In a six-zone virtual panel,
three-zone panel 1 can keep initial zone with the default value (1) and the three-
zone panel 2 requires changing initial zone from 1 to 4.
Note that this setting can be used to configure control panels to repeat the status
of control panels in the fire network with the zone LEDs. Consult fire network
advanced configuration settings for further details.
Basic fire network configuration will have the default fire network settings or the
ones previously configured in the advanced fire network configuration options.
Default fire network settings are as follows:
• Both control panels will control each other (fire panel and repeater panel).
• The network topology will be class B.
• The fire panel will repeat faults in the repeater panel.
• The fire panel will enter alarm and generate activations with remote zones.
• The fire panel will control its outputs (no addressable system in the network).
Firenet group
Use this menu to configure the initial node of a 32-node group inside the 250-
node network, if necessary.
To configure the Firenet group:
1. Set the display as shown below, and then press Enter.
2. Select a value using the value selection buttons (2 and 4). The Network fault
LED flashes fast to indicate that the Firenet group menu active.
3. Press Enter.
4. Save your changes.
Firenet analogue remote node
Use this menu to configure a remote panel out of its 32-node group inside the
250-node network.
To configure the Firenet analogue remote node:
1. Set the display as shown below, and then press Enter.
Summary of Contents for 1 3E Series
Page 1: ...1X X3E Series Installation Manual P N 501 419303 1 20 ISS 20JUL21 ...
Page 86: ...Chapter 4 Maintenance 80 1X X3E Series Installation Manual ...
Page 106: ...Appendix A Configuration presets 100 1X X3E Series Installation Manual ...
Page 110: ...Appendix B Regulatory information 104 1X X3E Series Installation Manual ...
Page 113: ......
Page 114: ......