Application Guide
P12y/EN AP/D32
MiCOM P125/P126 & P127
Page 39/74
5.
Reclaim Time tR
When the tD timer is expired, a close command is launched to the CB by an output
relay, the reclaim time (
tR
) will begin to count when the 52a input will be energized. It
will mean that the CB is closed.
When the close command is launched the tClose Pulse timer begins to count too. This
timer takes a look to the change of the 52a status from low to high, if the timer expired
before changing of the 52a, a time out condition has occurred and the ARC function
will move to the locked status. Otherwise the timer will be reset and the ARC will
continue with the setting cycles.
The setting for the t Close Pulse timer is available in the Automatic Control CB
Supervision submenu.
If during the tR the 52a will change status from high to low (CB from close to open
status), the ARC will move to the lock status.
If none phase or earth current threshold, earth power threshold or external digital input
will trip within the reclaim time, at the expiring of tR, the autoreclose function resets to
the initial status ready to re-start for a new cycles sequence.
6.
Inhibit Time tI
The Inhibit time starts when an intentional closing action is executed on the CB. Any
trip opening the CB within the tI timer will move the ARC in the lock status. The setting
value of the
Inhibit Time (tI)
can be used to prevent autoreclose being initiated when
the CB is manually closed onto a fault.
7.
Phase and earth fault cycles number
The maximum available auto-recloser cycles in the ARC in the P126 and P127 are 4.
The user can set 4 cycles for the earth faults and 4 cycles for the phase faults or
other. The auto-recloser algorithm will execute a maximum of 4 cycles.
What does it mean?
It means, for instance, we have set 4 auto-recloser cycles for earth fault and 4 auto-
recloser cycles for phase fault.
During a fault situation we have already executed 2 autoreclose cycles for a phase
fault, if the next fault will be an earth fault the ARC will be able to execute the
remaining ones. The number of set cycles, earth and/or phase, must be in accordance
with the set of the ARC configuration matrix setting. The setting to 0 of the phase
cycles and/or the earth cycles means that any trip of phase or earth are considered
final trip. The autoreclose will move in the lock status.
8.
ARC configuration matrix
From the 6A software version it has been implemented the possibility to assign to any
phase current threshold, to any earth fault current/power threshold and to the tAux1
and tAux2 the cycle where to have a recloser action or a definitive trip or a trip without
the relevant activation of the relay 1. The listed table below shows the involved
thresholds and the relevant setting way.
Summary of Contents for MiCOM P125
Page 1: ...MiCOM P125 P126 P127 Directional Non directional Relay Technical Guide P12Y EN T E32...
Page 2: ......
Page 4: ...P12y EN T E32 Technical Guide Page 2 2 MiCOM P125 P126 P127 BLANK PAGE...
Page 5: ...Pxxxx EN SS B11 SAFETY SECTION...
Page 6: ......
Page 8: ...Pxxxx EN SS B11 Page 2 10 Safety Section BLANK PAGE...
Page 16: ...Pxxxx EN SS B11 Page 10 10 Safety Section BLANK PAGE...
Page 17: ...Getting Started P12y EN GS D32 MiCOM P125 P126 P127 GETTING STARTED...
Page 18: ......
Page 66: ...P12y EN GS D32 Getting Started Page 48 48 MiCOM P125 P126 P127 BLANK PAGE...
Page 68: ......
Page 79: ...User Guide P12y EN FT D32 MiCOM P125 P126 P127 USER GUIDE...
Page 80: ......
Page 166: ...P12y EN FT D32 User Guide Page 86 86 MiCOM P125 P126 P127 BLANK PAGE...
Page 167: ...Technical Data P12y EN TD D32 MiCOM P125 P126 P127 TECHNICAL DATA AND CHARACTERISTIC CURVES...
Page 168: ......
Page 197: ...Application Guide P12y EN AP D32 MiCOM P125 P126 P127 APPLICATION GUIDE...
Page 198: ......
Page 202: ...P12y EN AP D32 Application Guide Page 4 74 MiCOM P125 P126 P127 BLANK PAGE...
Page 274: ......
Page 298: ...P12y EN CM C22 Commissioning and Maintenance Page 24 24 MiCOM P125 P126 P127 BLANK PAGE...
Page 300: ......
Page 302: ...P12y EN CO C22 Connections and Wiring Diagrams Page 2 10 MiCOM P125 P126 P127 BLANK PAGE...
Page 310: ...P12y EN CO C22 Connections and Wiring Diagrams Page 10 10 MiCOM P125 P126 P127 BLANK PAGE...
Page 312: ......
Page 360: ...P12y EN RS D32 Commissioning Test and Record Sheet Page 48 48 MiCOM P125 P126 P127 BLANK PAGE...
Page 361: ......