P12y/EN FT/D32
User Guide
Page 14/86
MiCOM P125/P126 & P127
4.2.1
Submenu General Options
The following submenu displays the connection mode only for the P127 and the default
display only for the P126.
The General Options submenu is not available for the P125 relay. The default display is fixed
to IN and there is no VT connection setting choice.
CONFIGURATION
Heading of CONFIGURATION menu.
To gain access to the General Options submenu, press
"
and
$
until the submenu is reached.
General Options
Heading of General Options submenu.
To navigate within submenu points, press
!
"
. To modify
setting, press
%
. Use
!
"
#
$
to scroll and set available
selections. Press
%
to confirm choice.
VT Connection
2Vpp+Vr
Displays the type of VT connection.
Select choice using the above instructions.
The available options are: 3Vpn, 2Vpp+Vr, 2Vpn+Vr.
To gain access to the next window press
"
. To gain
access to the previous window press
!
.
Default Displays
RMS I A
Displays the default current value (by selecting either Phase
A, Phase B, Phase C, or Earth N).
To modify this default value, follow the above instructions.
To gain access to the next window press
"
. To gain
access to the previous window press
!
.
4.2.2
Submenu Transfo. Ratio
CONFIGURATION
Heading of CONFIGURATION menu.
To gain access to the Transfo. Ratio submenu, press
"
and
$
until the submenu is reached.
Transfo. Ratio
Heading of Transfo. Ratio submenu.
To navigate within submenu points, press
!
"
. To modify
setting, press
%
. Use
!
"
#
$
to scroll and set available
selections. Press
%
to confirm choice.
To gain access to the next window press
"
. To gain
access to the previous window press
!
.
Line CT primary
5
A
Displays the rated primary current of the line CT.
The setting range is from 1 to 9999.
This setting is only available in P126 and P127 relays.
Line CT sec
5
A
Displays the rated secondary current of the line CT.
The setting value is either 1or 5.
This setting is only available in P126 and P127 relays.
E/Gnd CT primary
5
A
Displays the rated primary current of the earth CT.
The setting range is from 1 to 9999.
E/Gnd CT sec
5
A
Displays the rated secondary current of the earth CT.
The setting value is either 1 or 5.
The following displays and settings are only shown and applicable with the P127 relay.
Line VT primary
0.10
kV
Displays the rated primary voltage of the line VT. The rated
voltage input range is given by relay Cortec code.
The setting range is from 0.1to1000kV, in steps of 0.01kV.
For the 220-480V model the setting range is from 220 to
480V, in steps of 1V.
Line VT sec
100.0
V
Displays the rated secondary voltage of the line VT. The
rated voltage input range is given by relay Cortec code.
The setting range is from 57 to 130V, in steps of 0.1V
This window is not available for the 220-480V model.
Summary of Contents for MiCOM P125
Page 1: ...MiCOM P125 P126 P127 Directional Non directional Relay Technical Guide P12Y EN T E32...
Page 2: ......
Page 4: ...P12y EN T E32 Technical Guide Page 2 2 MiCOM P125 P126 P127 BLANK PAGE...
Page 5: ...Pxxxx EN SS B11 SAFETY SECTION...
Page 6: ......
Page 8: ...Pxxxx EN SS B11 Page 2 10 Safety Section BLANK PAGE...
Page 16: ...Pxxxx EN SS B11 Page 10 10 Safety Section BLANK PAGE...
Page 17: ...Getting Started P12y EN GS D32 MiCOM P125 P126 P127 GETTING STARTED...
Page 18: ......
Page 66: ...P12y EN GS D32 Getting Started Page 48 48 MiCOM P125 P126 P127 BLANK PAGE...
Page 68: ......
Page 79: ...User Guide P12y EN FT D32 MiCOM P125 P126 P127 USER GUIDE...
Page 80: ......
Page 166: ...P12y EN FT D32 User Guide Page 86 86 MiCOM P125 P126 P127 BLANK PAGE...
Page 167: ...Technical Data P12y EN TD D32 MiCOM P125 P126 P127 TECHNICAL DATA AND CHARACTERISTIC CURVES...
Page 168: ......
Page 197: ...Application Guide P12y EN AP D32 MiCOM P125 P126 P127 APPLICATION GUIDE...
Page 198: ......
Page 202: ...P12y EN AP D32 Application Guide Page 4 74 MiCOM P125 P126 P127 BLANK PAGE...
Page 274: ......
Page 298: ...P12y EN CM C22 Commissioning and Maintenance Page 24 24 MiCOM P125 P126 P127 BLANK PAGE...