User Guide
P12y/EN FT/D32
MiCOM P125/P126 & P127
Page 39/86
4.6.2.1
Threshold Menu Ie> DMT
Delay Type
DMT
Displays threshold delay time type. Setting choices are:
DMT (definite time), RI for the electromechanical inverse
time curve, IEC-XX, CO2, CO8, IEEE-XX inverse time delay
curve and RECT curve.
If the user selects DMT the following menu is displayed:
t Ie>
150.00
s
Displays setting value for the trip threshold.
The setting range is from 0 to 150 s, in steps of 10 ms.
tReset
0.10
s
Displays setting value for the reset time.
The setting range is from 0 to 100 s, in steps of 10 ms.
By pushing
"
the next window will display the Ie>>?
4.6.2.2
Threshold Menu Ie> RI
Delay Type
RI
Displays threshold delay time type. Setting choices are:
DMT (definite time), RI for the electromechanical inverse
time curve, IEC-XX, CO2, CO8, IEEE-XX inverse time delay
curve and RECT curve.
If the user selects RI the following menu is displayed.
K
1.000
Selection of K value for the RI curve.
The setting range is from 0.100 to 10 in steps of 0.005.
tReset
0.10
s
Displays setting value for the reset time.
The setting range is from 0 to 100 s, in steps of 10ms.
Ie> >> >>>
Interlock
Yes
Interlock of first threshold by the second and third
thresholds, but only if first threshold trip is set to IDMT.
Setting choice: No, Yes
By pushing
"
the next window will display the Ie>>?
4.6.2.3
Threshold Menu Ie> IEC-XX
Delay Type
IEC-STI
Displays threshold delay time type. Setting choices are:
DMT (definite time) RI for the electromechanical inverse
time curve, IEC-XX, CO2, CO8, IEEE-XX inverse time delay
curve and RECT curve.
If the user selects IEC curve the following menu is
displayed:
TMS
1.000
Displays TMS value for the curve.
The setting range is from 0.025 to 1.5, in steps of 0.025.
tReset
0.10
s
Displays setting value for the reset time.
The setting range is from 0 to 100 s, in steps of 10 ms.
Ie> >> >>>
Interlock
Yes
Interlock of first threshold by the second and third
thresholds, but only if first threshold trip is set to IDMT.
Setting choice: No, Yes
By pushing
"
the next window will display the Ie>>?
Summary of Contents for MiCOM P125
Page 1: ...MiCOM P125 P126 P127 Directional Non directional Relay Technical Guide P12Y EN T E32...
Page 2: ......
Page 4: ...P12y EN T E32 Technical Guide Page 2 2 MiCOM P125 P126 P127 BLANK PAGE...
Page 5: ...Pxxxx EN SS B11 SAFETY SECTION...
Page 6: ......
Page 8: ...Pxxxx EN SS B11 Page 2 10 Safety Section BLANK PAGE...
Page 16: ...Pxxxx EN SS B11 Page 10 10 Safety Section BLANK PAGE...
Page 17: ...Getting Started P12y EN GS D32 MiCOM P125 P126 P127 GETTING STARTED...
Page 18: ......
Page 66: ...P12y EN GS D32 Getting Started Page 48 48 MiCOM P125 P126 P127 BLANK PAGE...
Page 68: ......
Page 79: ...User Guide P12y EN FT D32 MiCOM P125 P126 P127 USER GUIDE...
Page 80: ......
Page 166: ...P12y EN FT D32 User Guide Page 86 86 MiCOM P125 P126 P127 BLANK PAGE...
Page 167: ...Technical Data P12y EN TD D32 MiCOM P125 P126 P127 TECHNICAL DATA AND CHARACTERISTIC CURVES...
Page 168: ......
Page 197: ...Application Guide P12y EN AP D32 MiCOM P125 P126 P127 APPLICATION GUIDE...
Page 198: ......
Page 202: ...P12y EN AP D32 Application Guide Page 4 74 MiCOM P125 P126 P127 BLANK PAGE...
Page 274: ......
Page 298: ...P12y EN CM C22 Commissioning and Maintenance Page 24 24 MiCOM P125 P126 P127 BLANK PAGE...
Page 300: ......
Page 302: ...P12y EN CO C22 Connections and Wiring Diagrams Page 2 10 MiCOM P125 P126 P127 BLANK PAGE...
Page 310: ...P12y EN CO C22 Connections and Wiring Diagrams Page 10 10 MiCOM P125 P126 P127 BLANK PAGE...
Page 312: ......
Page 360: ...P12y EN RS D32 Commissioning Test and Record Sheet Page 48 48 MiCOM P125 P126 P127 BLANK PAGE...
Page 361: ......