User Guide
Page 22/86
MiCOM P125/P126 & P127
Start/Stop
tAUX2
By Input
LEVEL
To modify press
%
and using
!
"
keys to select if the
control of the timer is on the change of the LEVEL of the
relevant input or on the EDGE of the relevant input.
Press
%
to confirm the setting.
Start/Stop
tAUX3
By Input
LEVEL
To modify press
%
and using
!
"
keys to select if the
control of the timer is on the change of the LEVEL of the
relevant input or on the EDGE of the relevant input.
Press
%
to confirm the setting.
Start/Stop
tAUX4
By Input
LEVEL
To modify press
%
and using
!
"
keys to select if the
control of the timer is on the change of the LEVEL of the
relevant input or on the EDGE of the relevant input
Press
%
to confirm the setting.
It is possible to configure the operation of the digital input, either on falling edge/low level, or
on rising edge/high level.
Falling edge or low level (idem for rising edge or high level) depends of the application of the
digital inputs.
Example : a digital input configured "blocking logic" will operate on level, on the other hand a
digital input configured "Cold load pick up" will operate on edge.
ONLY a digital input configured "change of setting group" can operate either on edge
or on level.
Function allocated to the Digital Input
Operation of the Digital Input
Unlatch of the output relays
On level
Position of the CB, 52a or 52b
On level
Blocking logic 1 & 2
On level
Logic Selectivity 1 & 2
On level
Aux 1, Aux 2, Aux3 & Aux4
On level / On Edge
CB Fault
On level
Reset of the thermal state
On edge
Cold load Pick Up
On edge
Start of disturbance record
On edge
Trip circuit supervision
On level
Change of setting group
On edge, or on level
CB Fail timer start
On edge
Block 79
On level
Maintenace Mode
On level
Man. close
On edge
Local On
level
The user has to set in the CONFIGURATION Menu the auxiliary voltage (AC or DC) for the
operation of the digital inputs. This setting is necessary due to the time filtering different in
DC and AC.
Summary of Contents for MiCOM P125
Page 1: ...MiCOM P125 P126 P127 Directional Non directional Relay Technical Guide P12Y EN T E32...
Page 2: ......
Page 4: ...P12y EN T E32 Technical Guide Page 2 2 MiCOM P125 P126 P127 BLANK PAGE...
Page 5: ...Pxxxx EN SS B11 SAFETY SECTION...
Page 6: ......
Page 8: ...Pxxxx EN SS B11 Page 2 10 Safety Section BLANK PAGE...
Page 16: ...Pxxxx EN SS B11 Page 10 10 Safety Section BLANK PAGE...
Page 17: ...Getting Started P12y EN GS D32 MiCOM P125 P126 P127 GETTING STARTED...
Page 18: ......
Page 66: ...P12y EN GS D32 Getting Started Page 48 48 MiCOM P125 P126 P127 BLANK PAGE...
Page 68: ......
Page 79: ...User Guide P12y EN FT D32 MiCOM P125 P126 P127 USER GUIDE...
Page 80: ......
Page 166: ...P12y EN FT D32 User Guide Page 86 86 MiCOM P125 P126 P127 BLANK PAGE...
Page 167: ...Technical Data P12y EN TD D32 MiCOM P125 P126 P127 TECHNICAL DATA AND CHARACTERISTIC CURVES...
Page 168: ......
Page 197: ...Application Guide P12y EN AP D32 MiCOM P125 P126 P127 APPLICATION GUIDE...
Page 198: ......
Page 202: ...P12y EN AP D32 Application Guide Page 4 74 MiCOM P125 P126 P127 BLANK PAGE...
Page 274: ......
Page 298: ...P12y EN CM C22 Commissioning and Maintenance Page 24 24 MiCOM P125 P126 P127 BLANK PAGE...
Page 300: ......
Page 302: ...P12y EN CO C22 Connections and Wiring Diagrams Page 2 10 MiCOM P125 P126 P127 BLANK PAGE...
Page 310: ...P12y EN CO C22 Connections and Wiring Diagrams Page 10 10 MiCOM P125 P126 P127 BLANK PAGE...
Page 312: ......
Page 360: ...P12y EN RS D32 Commissioning Test and Record Sheet Page 48 48 MiCOM P125 P126 P127 BLANK PAGE...
Page 361: ......