5.13
Switch onto Fault Protection & Trip on Reclose (SOTF/TOR) (P126 & P127)
5.13.1 General
It can happen, in particular plan conditions that when the feeder is supplied by the closing of
the CB a fast tripping may be required if a fault is present. (Closing on to fault)
Some faults may be due to conditions not removed from the feeder after a reclosing cycle or
manual tripping, or due to earthing clamps left on following maintenance works. In these
cases, it may be desirable to clear the fault condition in fast time, rather than waiting for the
trip delay time DMT or IDMT associated with the involved protection.
In the case of manually closing of the CB it can happen to switch on to an existing fault. This
is a particularly critical situation, because the overcurrent protection would not clear the fault
until the set operate delay had elapsed. This is another typical case of closing on to fault.
Hence the fastest possible clearance of the fault is desirable.
The P126 and P127 relays provide the SOTF/TOR functionality.
The SOTF acronym means switch on to fault.
The TOR acronym means trip on recloser.
The available setting to enable/disable/set the SOTF/TOR function is written in a submenu of
the AUTOMATIC CTRL menu.
The setting regarding the I>> and I>>> is provided to initiate the Sotf function.
5.13.2 SOTF/TOR
description
The SOTF/TOR function can be initiated by a local manual control close CB detected by the
digital input Man. Close, or by a TC (closing command by remote via network: Modbus, IEC
60870, DNP3, Courier) or by an automatic reclosing cycle.
When CB has closed to some faults caused by flash or something else, the detection of the
fault needs of a time period, this is the reason because a time window after initiation of the
SOTF/TOR function is included.
This time window is realised by a fixed timer with a delay time of 500ms.
When this fixed timer is elapsed and the I>> or I>>> is detected, the timer settable t Sotf
starts.
The reason of existence of this settable timer is justified because in some application
selectivity for fault occurring in stage two or three is requested.
Another justification of the using of the SOTF/TOR tripping time delay is for some cases
where serious transient happen, the three poles of the CB do not close to the same time and
in those cases where the CB may not be closed instantaneously.
Further, the t SOFT can also be considered a trip delay time that substitutes the trip timer of
the started threshold such to accelerate the tripping.
If a trip due to switch on to fault occurs during the reclaim time of the ARC, the trip will be
definitive and the ARC will be locked.
If the I>> and I>>> reset during the settable timer t Sotf the SOTF/TOR function resets.
The SOTF/TOR functionality diagram is shown below.
Summary of Contents for MiCOM P125
Page 1: ...MiCOM P125 P126 P127 Directional Non directional Relay Technical Guide P12Y EN T E32...
Page 2: ......
Page 4: ...P12y EN T E32 Technical Guide Page 2 2 MiCOM P125 P126 P127 BLANK PAGE...
Page 5: ...Pxxxx EN SS B11 SAFETY SECTION...
Page 6: ......
Page 8: ...Pxxxx EN SS B11 Page 2 10 Safety Section BLANK PAGE...
Page 16: ...Pxxxx EN SS B11 Page 10 10 Safety Section BLANK PAGE...
Page 17: ...Getting Started P12y EN GS D32 MiCOM P125 P126 P127 GETTING STARTED...
Page 18: ......
Page 66: ...P12y EN GS D32 Getting Started Page 48 48 MiCOM P125 P126 P127 BLANK PAGE...
Page 68: ......
Page 79: ...User Guide P12y EN FT D32 MiCOM P125 P126 P127 USER GUIDE...
Page 80: ......
Page 166: ...P12y EN FT D32 User Guide Page 86 86 MiCOM P125 P126 P127 BLANK PAGE...
Page 167: ...Technical Data P12y EN TD D32 MiCOM P125 P126 P127 TECHNICAL DATA AND CHARACTERISTIC CURVES...
Page 168: ......
Page 197: ...Application Guide P12y EN AP D32 MiCOM P125 P126 P127 APPLICATION GUIDE...
Page 198: ......
Page 202: ...P12y EN AP D32 Application Guide Page 4 74 MiCOM P125 P126 P127 BLANK PAGE...
Page 274: ......
Page 298: ...P12y EN CM C22 Commissioning and Maintenance Page 24 24 MiCOM P125 P126 P127 BLANK PAGE...
Page 300: ......
Page 302: ...P12y EN CO C22 Connections and Wiring Diagrams Page 2 10 MiCOM P125 P126 P127 BLANK PAGE...
Page 310: ...P12y EN CO C22 Connections and Wiring Diagrams Page 10 10 MiCOM P125 P126 P127 BLANK PAGE...
Page 312: ......
Page 360: ...P12y EN RS D32 Commissioning Test and Record Sheet Page 48 48 MiCOM P125 P126 P127 BLANK PAGE...
Page 361: ......