Inhib Time
tI 5.00
s
Displays setting value of the inhibit time (tI) for the
autoreclose function (following a manual CB closure).
Setting range from 0.01 s to 600 s, in steps of 10 ms.
4.6.11.4 [79] Phase and Earth Re-closing Cycles
Phase Cycles
4
Displays setting of autoreclose cycles externally started by
a phase protection trip signal.
Setting choice is from 0 to 4 cycles.
E/Gnd Cycles
4
Displays setting of autoreclose cycles externally started by
an earth protection trip signal.
Setting choice is from 0 to 4 cycles.
By pushing
"
the next window will display the [79] cycles allocation
4.6.11.5 [79] Cycles allocation
CYCLES
4321
tI>
1101
0 = no action on autorecloser : definitive trip
1 = trip on tI> pick-up, followed by reclosing cycle
2 = no trip on tI> pick-up
CYCLES
4321
tI>>
1101
0 = no action on autorecloser : definitive trip
1 = trip on tI>> pick-up, followed by reclosing cycle
2 = no trip on tI>> pick-up
CYCLES
4321
tI>>>
1101
0 = no action on autorecloser : definitive trip
1 = trip on tI>>> pick-up, followed by reclosing cycle
2 = no trip on tI>>> pick-up
CYCLES
4321
tIe>
1101
0 = no action on autorecloser : definitive trip
1 = trip on tIe> pick-up, followed by reclosing cycle
2 = no trip on tIe> pick-up
CYCLES
4321
tIe>>
1101
0 = no action on autorecloser : definitive trip
1 = trip on tIe>> pick-up, followed by reclosing cycle
2 = no trip on tIe>> pick-up
CYCLES
4321
tIe>>>
1101
0 = no action on autorecloser : definitive trip
1 = trip on tIe>>> pick-up, followed by reclosing cycle
2 = no trip on tIe>>> pick-up
CYCLES
4321
tPe/Iecos>
1101
0 = no action on autorecloser : definitive trip
1 = trip on tPe/Iecos> pick-up, followed by reclosing cycle
2 = no trip on tPe/Iecos> pick-up
CYCLES
4321
tPe/Iecos>> 1101
0 = no action on autorecloser : definitive trip
1 = trip on tPe/Iecos>> pick-up, followed by reclosing cycle
2 = no trip on tPe/Iecos>>pick-up
CYCLES
4321
tAux1 1101
0 = no action on autorecloser : definitive trip
1 = trip on tAux1 pick-up, followed by reclosing cycle
2 = no trip on tAux1 pick-up
CYCLES
4321
tAux2 1101
0 = no action on autorecloser : definitive trip
1 = trip on tAux2 pick-up, followed by reclosing cycle
2 = no trip on tAux2 pick-up
By pushing
"
the next window will display the [79] Autoreclose.
Summary of Contents for MiCOM P125
Page 1: ...MiCOM P125 P126 P127 Directional Non directional Relay Technical Guide P12Y EN T E32...
Page 2: ......
Page 4: ...P12y EN T E32 Technical Guide Page 2 2 MiCOM P125 P126 P127 BLANK PAGE...
Page 5: ...Pxxxx EN SS B11 SAFETY SECTION...
Page 6: ......
Page 8: ...Pxxxx EN SS B11 Page 2 10 Safety Section BLANK PAGE...
Page 16: ...Pxxxx EN SS B11 Page 10 10 Safety Section BLANK PAGE...
Page 17: ...Getting Started P12y EN GS D32 MiCOM P125 P126 P127 GETTING STARTED...
Page 18: ......
Page 66: ...P12y EN GS D32 Getting Started Page 48 48 MiCOM P125 P126 P127 BLANK PAGE...
Page 68: ......
Page 79: ...User Guide P12y EN FT D32 MiCOM P125 P126 P127 USER GUIDE...
Page 80: ......
Page 166: ...P12y EN FT D32 User Guide Page 86 86 MiCOM P125 P126 P127 BLANK PAGE...
Page 167: ...Technical Data P12y EN TD D32 MiCOM P125 P126 P127 TECHNICAL DATA AND CHARACTERISTIC CURVES...
Page 168: ......
Page 197: ...Application Guide P12y EN AP D32 MiCOM P125 P126 P127 APPLICATION GUIDE...
Page 198: ......
Page 202: ...P12y EN AP D32 Application Guide Page 4 74 MiCOM P125 P126 P127 BLANK PAGE...
Page 274: ......
Page 298: ...P12y EN CM C22 Commissioning and Maintenance Page 24 24 MiCOM P125 P126 P127 BLANK PAGE...
Page 300: ......
Page 302: ...P12y EN CO C22 Connections and Wiring Diagrams Page 2 10 MiCOM P125 P126 P127 BLANK PAGE...
Page 310: ...P12y EN CO C22 Connections and Wiring Diagrams Page 10 10 MiCOM P125 P126 P127 BLANK PAGE...
Page 312: ......
Page 360: ...P12y EN RS D32 Commissioning Test and Record Sheet Page 48 48 MiCOM P125 P126 P127 BLANK PAGE...
Page 361: ......