User Guide
P12y/EN FT/D32
MiCOM P125/P126 & P127
Page 81/86
4.8.1.1
Submenu Fault Record for P126 & P127
The Fault Record submenu makes it possible to read up to five stored fault records, that
occurred when programmed thresholds where exceeded.
The fault records are generated by the operation of trip relay RL1.
NOTE:
All measurement magnitude values refer to the transformer primary
side.
RECORD
Heading of RECORD menu.
Fault Record
Heading of Fault Record submenu
To gain access to the submenu points, press
"
.
Record Number
5
Selection of the Fault Record number 5 to be displayed
(selection: 1, 2, 3, 4 or 5). To modify this fault record
number, press
&
then using
!
the required number is
entered. Press
%
to confirm choice.
Fault Time
13:05:23
Displays the time when the fault was recorded. The format
of the time is hh:mm:ss.
In this example the fault was recorded at 1:05:23 pm.
Fault Date
12/11/01
Displays the date when the fault was recorded. The format
of the Date is DD/MM/YY.
In this example, the fault was recorded on November 12th
2001.
Active Set Group
1
Displays the active setting group (1 or 2).
Faulted Phase
PHASE
A
Displays the phase, where a fault occurred, for the chosen
fault record. (NONE, PHASE A, B, C, EARTH)
Threshold
-----
Displays the origin of the fault that generated the trip order.
Common for P126 & P127 are:
tIe>, tIe>>, tIe>>>, tPe/IeCos>, tPe/IeCos>>, Trip tUe>>>>,
tI>, tI>>, tI>>>, tI<, tI2>, tI2>>, tI2>>>, Thermal
θ
, Brkn.
Cond, tAux 1, tAux 2, tAux 3, tAux 4, EQU A, EQU B, EQU
C, EQU D
Only valid for P127:
tU>, tU>>, tU<, tU<<
Magnitude
1200
A
Displays the magnitude value of the fault: Voltage, current,
earth power. The value is based on the amplitude at 50 or
60 Hz.
IA Magnitude
1200
A
Displays the magnitude value of the phase A current at the
time of the fault.
IB Magnitude
1200
A
Displays the magnitude value of the phase B current at the
time of the fault.
IC Magnitude
1280
A
Displays the magnitude value of the phase C current at the
time of the fault.
IN Magnitude
103
A
Displays the magnitude value of the earth current at the
time of the fault.
VAB Magnitude
10
KV
Only P127
Displays the magnitude value of the phase A to phase B
voltage at the time of the fault.
VBC Magnitude
10
KV
Only P127
Displays the magnitude value of the phase B to phase C
voltage at the time of the fault.
Summary of Contents for MiCOM P125
Page 1: ...MiCOM P125 P126 P127 Directional Non directional Relay Technical Guide P12Y EN T E32...
Page 2: ......
Page 4: ...P12y EN T E32 Technical Guide Page 2 2 MiCOM P125 P126 P127 BLANK PAGE...
Page 5: ...Pxxxx EN SS B11 SAFETY SECTION...
Page 6: ......
Page 8: ...Pxxxx EN SS B11 Page 2 10 Safety Section BLANK PAGE...
Page 16: ...Pxxxx EN SS B11 Page 10 10 Safety Section BLANK PAGE...
Page 17: ...Getting Started P12y EN GS D32 MiCOM P125 P126 P127 GETTING STARTED...
Page 18: ......
Page 66: ...P12y EN GS D32 Getting Started Page 48 48 MiCOM P125 P126 P127 BLANK PAGE...
Page 68: ......
Page 79: ...User Guide P12y EN FT D32 MiCOM P125 P126 P127 USER GUIDE...
Page 80: ......
Page 166: ...P12y EN FT D32 User Guide Page 86 86 MiCOM P125 P126 P127 BLANK PAGE...
Page 167: ...Technical Data P12y EN TD D32 MiCOM P125 P126 P127 TECHNICAL DATA AND CHARACTERISTIC CURVES...
Page 168: ......
Page 197: ...Application Guide P12y EN AP D32 MiCOM P125 P126 P127 APPLICATION GUIDE...
Page 198: ......
Page 202: ...P12y EN AP D32 Application Guide Page 4 74 MiCOM P125 P126 P127 BLANK PAGE...
Page 274: ......
Page 298: ...P12y EN CM C22 Commissioning and Maintenance Page 24 24 MiCOM P125 P126 P127 BLANK PAGE...
Page 300: ......
Page 302: ...P12y EN CO C22 Connections and Wiring Diagrams Page 2 10 MiCOM P125 P126 P127 BLANK PAGE...
Page 310: ...P12y EN CO C22 Connections and Wiring Diagrams Page 10 10 MiCOM P125 P126 P127 BLANK PAGE...
Page 312: ......
Page 360: ...P12y EN RS D32 Commissioning Test and Record Sheet Page 48 48 MiCOM P125 P126 P127 BLANK PAGE...
Page 361: ......