Application Guide
P12y/EN AP/D32
MiCOM P125/P126 & P127
Page 35/74
4.
DESCRIPTION AND SETTING GUIDE OF THE AUTORECLOSE
FUNCTION (P126 & P127)
An analysis of faults on any overhead line network has shown that 80 - 90% are transient in
nature. A transient fault, such as an insulator flashover, is a self-clearing ‘non-damage’ fault.
This type of fault can be cleared by the immediate tripping of one or more circuit breakers to
isolate the fault, and does not recur when the line is re-energised. Lightning is the most
common cause of transient faults, other possible causes being clashing conductors and wind
blown debris. The remaining 10 - 20% of faults are either non-permanent (arcing fault) or
permanent.
A small tree branch falling on the line could cause a non-permanent fault. Here the cause of
the fault would not be removed by the immediate tripping of the circuit, but could be burnt
away during a time-delayed trip.
Permanent faults could be broken conductors, transformer faults, cable faults or machine
faults that must be located and repaired before the supply can be restored.
In the majority of fault incidents, if the faulty line is immediately tripped out, and time is
allowed for the fault arc to de-ionise, re-closure of the circuit breakers will result in the line
being successfully re-energised. Autoreclose approaches are employed to automatically re-
close a switching device at a set time after it has been opened due to operation of protection
where transient and non-permanent faults are prevalent.
On HV and MV distribution networks, the autoreclose function is applied mainly to radial
feeders where system stability problems do not generally arise. The main advantages to be
derived from using autoreclose can be summarised as follows:
•
Minimises interruptions in supply to the consumer.
•
Reduces operating costs - less man-hours in repairing fault damage and the possibility
of running substations unattended. With autoreclose instantaneous protection can be
used which means shorter fault durations which gives rise to less fault damage and
fewer permanent faults.
As 80% of overhead line faults are transient, elimination of loss of supply from such faults, by
the introduction of the autoreclose function gives obvious benefits. Furthermore, autoreclose
may allow a particular substation to operate unattended. In the case of unattended
substations, the number of visits by personnel to re-close a circuit breaker manually after a
fault can be substantially reduced, which is an important consideration for substations in
remote areas.
The autoreclose function gives an important benefit on circuits using time-graded protection,
in that it allows the use of instantaneous protection to give a high-speed first trip. With fast
tripping, the duration of the power arc resulting from an overhead line fault is reduced to a
minimum, thus lessening the chance of damage to the line, which might otherwise cause a
transient fault to develop into a permanent fault.
Using short time delay protection also prevents blowing of fuses and reduces circuit breaker
maintenance by eliminating pre-arc heating when clearing transient faults.
Summary of Contents for MiCOM P125
Page 1: ...MiCOM P125 P126 P127 Directional Non directional Relay Technical Guide P12Y EN T E32...
Page 2: ......
Page 4: ...P12y EN T E32 Technical Guide Page 2 2 MiCOM P125 P126 P127 BLANK PAGE...
Page 5: ...Pxxxx EN SS B11 SAFETY SECTION...
Page 6: ......
Page 8: ...Pxxxx EN SS B11 Page 2 10 Safety Section BLANK PAGE...
Page 16: ...Pxxxx EN SS B11 Page 10 10 Safety Section BLANK PAGE...
Page 17: ...Getting Started P12y EN GS D32 MiCOM P125 P126 P127 GETTING STARTED...
Page 18: ......
Page 66: ...P12y EN GS D32 Getting Started Page 48 48 MiCOM P125 P126 P127 BLANK PAGE...
Page 68: ......
Page 79: ...User Guide P12y EN FT D32 MiCOM P125 P126 P127 USER GUIDE...
Page 80: ......
Page 166: ...P12y EN FT D32 User Guide Page 86 86 MiCOM P125 P126 P127 BLANK PAGE...
Page 167: ...Technical Data P12y EN TD D32 MiCOM P125 P126 P127 TECHNICAL DATA AND CHARACTERISTIC CURVES...
Page 168: ......
Page 197: ...Application Guide P12y EN AP D32 MiCOM P125 P126 P127 APPLICATION GUIDE...
Page 198: ......
Page 202: ...P12y EN AP D32 Application Guide Page 4 74 MiCOM P125 P126 P127 BLANK PAGE...
Page 274: ......
Page 298: ...P12y EN CM C22 Commissioning and Maintenance Page 24 24 MiCOM P125 P126 P127 BLANK PAGE...
Page 300: ......
Page 302: ...P12y EN CO C22 Connections and Wiring Diagrams Page 2 10 MiCOM P125 P126 P127 BLANK PAGE...
Page 310: ...P12y EN CO C22 Connections and Wiring Diagrams Page 10 10 MiCOM P125 P126 P127 BLANK PAGE...
Page 312: ......
Page 360: ...P12y EN RS D32 Commissioning Test and Record Sheet Page 48 48 MiCOM P125 P126 P127 BLANK PAGE...
Page 361: ......