6RL SERIES OPERATION MANUAL
SECTION 7: REMOTE PROGRAMMING
Entire Contents Copyright
2018 by Adaptive Power Systems, Inc. (APS) • All Rights Reserved • No reproduction without written authorization from APS.
6RL Series Regenerative DC Load Operation Manual
Page 185 of 204
Bit configuration of the device status value:
Bit
Name
Meaning
Bit
Name
Meaning
31
Remote control
1 = on
15
-
30
Input / output
1 = on (req., register
405)
14
Alarm OVD
1 = alarm active
29
Volt. reg. speed
1 = fast (register 422)
13
Alarm OVP
1 = alarm active
28
UIP/UIR
1 = UIR (Register 409)
12
Alarm PF
1 = alarm active
27
Alarms
1 = at least 1 alarm
active
11
26
Alarm MSS
1 = alarm active
10
25
Alarm OCD
1 = alarm active
9
REMSB
1 = on (register 505, bit
30)
24
Alarm OCP
1 = alarm active
8
Alarm UCD
1 = alarm active
23
Interface in access
register 505, bits 4-0
7
Alarm UVD
1 = alarm active
22
6
Remote sensing
1 = external, 0 = internal
21
5
Function gen.
1 = FG active
20
4
MS type
1 = master, 0 = slave
19
3
Input / output
1 = on (register 505, bit 7)
18
Alarm OPD
1 = alarm active
2
Reg. mode
Register 505, bits 10-9
17
Alarm OPP
1 = alarm active
1
16
Alarm OT
1 = alarm active
0
-
Access: Base ID Cyclic Read + 1 (Actual values).
Bytes 0-1
Bytes 2-3
Bytes 4-5
Register 507
Register 508
Register 509
Actual voltage
Actual current
Actual power
Access: Base ID Cyclic Read + 2 (Set values)
Bytes 0-1
Bytes 2-3
Bytes 4-5
Bytes 6-7
Register 500
Register 501
Register 502
Register 503
Set value of voltage
Set value of current
Set value of power
Set value of resistance
Access: Base ID Cyclic Read + 3 (Adjustment limits 1)
Bytes 0-1
Bytes 2-3
Bytes 4-5
Bytes 6-7
Register 9002
Register 9003
Register 9000
Register 9001
I-max
I-min
U-max
U-min
Access: Base ID Cyclic Read + 4 (Adjustment limits 2)
Bytes 0-1
Bytes 2-3
Register 9004
Register 9006
P-max
R-max