6RL SERIES OPERATION MANUAL
SECTION 4: TECHNICAL SPECIFICATIONS
Entire Contents Copyright
2018 by Adaptive Power Systems, Inc. (APS) • All Rights Reserved • No reproduction without written authorization from APS.
6RL Series Regenerative DC Load Operation Manual
Page 26 of 204
4
Technical Specifications
Technical specifications shown here apply at an ambient temperature of 25° C ± 5°.
4.1
3.1kW Models - 208Vac Input (-2)
3.1 kW
Model
6RL03-170-80-2
6RL03-70-250-2
6RL03-30-500-2
6RL03-22-750-2
AC Input/Output
Input/output voltage
208 V, ±10%, L-L
208 V, ±10%, L-L
208 V, ±10%, L-L
208 V, ±10%, L-L
Input/output connection
L2, L3, PE
L2, L3, PE
L2, L3, PE
L2, L3, PE
Input/output frequency
50/60 Hz ±10%
50/60 Hz ±10%
50/60 Hz ±10%
50/60 Hz ±10%
Input/output fuse (internal)
T16 A
T16 A
T16 A
T16 A
Efficiency
(2
≤ 92.5%
≤ 93.5%
≤ 94.5%
≤ 94.5%
DC Input
Max. input voltage UMax
80 V
250 V
500 V
750 V
Max. input power PMax
3100 W
3100 W
3100 W
3100 W
Max. input current IMax
170 A
70 A
30 A
22 A
Overvoltage protection range
0...1.1 * UMax
0...1.1 * UMax
0...1.1 * UMax
0...1.1 * UMax
Overcurrent protection range
0...1.1 * IMax
0...1.1 * IMax
0...1.1 * IMax
0...1.1 * IMax
Overpower protection range
0...1.1 * PMax
0...1.1 * PMax
0...1.1 * PMax
0...1.1 * PMax
Max. allowed input voltage
100 V
300 V
600 V
850 V
Min. input voltage for IMax
0.73 V
2.3 V
4.6 V
6.8 V
Input capacitance
ca. 770 μF
ca. 310 μF
ca. 98 μF
ca. 60 μF
Temperature coefficient
for set values Δ / K
Voltage / current: 100 ppm
Voltage regulation
Adjustment range
0...80 V
0...250 V
0...500 V
0...750 V
Stability at ΔI
< 0.05% UMax
< 0.05% UMax
< 0.05% UMax
< 0.05% UMax
Accuracy
(1
(at 23 ± 5°C)
< 0.3% UMax
< 0.3% UMax
< 0.3% UMax
< 0.3% UMax
Display: Adjustment resolution
See section 6.2.6, “
Available resolutions by voltage models:
Display: Accuracy
(3
≤ 0.2%
Remote sensing compensation
max. 5% UMax
Current regulation
Adjustment range
0...170 A
0...70 A
0...30 A
0...22 A
Stability at ΔU
< 0.15% IMax
< 0.15% IMax
< 0.15% IMax
< 0.15% IMax
Accuracy
(1
(at 23 ± 5°C)
< 0.4% IMax
< 0.4% IMax
< 0.4% IMax
< 0.4% IMax
Display: Adjustment resolution
See section 6.2.6, “
Available resolutions by voltage models:
Display: Accuracy
(3
≤0.2%
Compensation 10-90% ΔUDC
< 0.6 ms
< 0.6 ms
< 0.6 ms
< 0.6 ms
Power regulation
Adjustment range
0…3100 W
0…3100 W
0…3100 W
0…3100 W
Stability at ΔI / ΔU
< 0.75% PMax
< 0.75% PMax
< 0.75% PMax
< 0.75% PMax
Accuracy
(1
(at 23 ± 5°C)
< 1.25% PMax
< 1.5% PMax
< 1.4% PMax
< 1.5% PMax
Display: Adjustment resolution
See section 6.2.6, “
Available resolutions by voltage models:
Display: Accuracy
(3
≤ 0.2%
Resistance regulation
Adjustment range
0.01…12 Ω
0.09…120 Ω
0.42…480 Ω
0.8…1100 Ω
Accuracy (at 23 ± 5°C)
≤2% of max. resistance ± 0.3% of maximum current
Display: Adjustment resolution
See section 6.2.6, “
Available resolutions by voltage models:
Display: Accuracy
(3
≤0.2%
Summary of Contents for 6RL Series