6RL SERIES OPERATION MANUAL
SECTION 6: FRONT PANEL OPERATION
Entire Contents Copyright
2018 by Adaptive Power Systems, Inc. (APS) • All Rights Reserved • No reproduction without written authorization from APS.
6RL Series Regenerative DC Load Operation Manual
Page 67 of 204
6.4.3.2
General Settings Menu
Setting
P.
Description
Allow remote control
1
Selection “NO” means that the unit cannot be remotely controlled over either the digital
or analog interfaces. If remote control is not allowed, the status will be shown as “local”
in the status area on the main display.
Analog interface range
1
Selects the voltage range for the analog set inputs, actual value outputs and reference
voltage output.
• 0...5 V = Range is 0...100% set /actual values, reference voltage 5 V
• 0...10 V = Range is 0...100% set /actual values, reference voltage 10 V.
See section also 6.5.3.
Analog interface Rem-SB
2
Selects how the input pin “Rem-SB” of the analog interface shall be working regarding
levels (See section 6.5.3) and logic:
• normal = Levels and function as described in the
• inverted = Levels and function will be inverted
Analog Rem-SB action
2
Selects the action on the DC input that is initiated when changing the level of analog input
“Rem-SB”:
• DC OFF = the pin can only be used to switch the DC output off
• DC AUTO = the pin can be used to switch the DC output off and on again, if it has been
switched on before at least from a different control location
DC Input after power ON
3
Determines the condition of the DC input after power-up.
• OFF = DC output is always off after switching on the unit.
• Restore = DC output condition will be restored to the condition prior to
switch off.
Voltage controller settings
3
Selects the regulation speed of the internal voltage regulator between “Slow”
and “Fast”. See section 3.4.1.1, “
DC Input after PF alarm
4
Determines how the DC input shall react after a power fail (PF) alarm has occurred:
• OFF = DC output will be switched off and remain until user action
• Auto ON = DC output will switch on again after the PF alarm cause is gone and if it was
switched on before the alarm occurred
DC Input after remote
4
Determines the condition of the DC output after leaving remote control either manually or
by command.
• OFF = DC input will be always off when switching from remote to manual
• AUTO = DC input will keep the last condition
Enable R mode
5
Activates (“Yes”) or deactivates (“No”) the internal resistance control. If activated, the
resistance set value can be adjusted on the main screen as additional value. For details,
refer to section 3.4.4 on page 20.
USB decimal point format
6
Switches the decimal point format of values and also the CSV file separator for USB
logging and for other features where CSV file can be loaded
US = Comma separator (US standard for CSV files)
Default = Semicolon separator (European standard for CSV files)
USB logging with units
(V,A,W)
6
CSV files generated from USB logging by default add physical units to values.
This can be deactivated by setting this option to “No”
Calibrate unit
7
Touch area “Start” starts a calibration routine (see
unit is in U/I or U/P mode.
Reset unit to defaults
8
Touch area “Start” will initiate a reset of all settings (HMI, profile etc.) to factory default, as
shown in the menu structure diagrams on the previous pages
Restart unit
8
Will initiate a warm start of the unit
Master-slave mode
9
Selecting “MASTER” or “SLAVE” enables the master-slave mode (MS) and sets the selected
position for the unit in the MS system. Default setting: OFF. This applies to the digital MS
bus, the analog Share bus and two-quadrants operation. For details, see section 8,
“