A - 31
Model 4500 MkIII
Opacity and Dust Monitor
User Guide
A5.5 Calibration Trigger Input
Connect volt-free contacts between A30 and A31 to initiate calibration check.
Terminal
Function
A29
Calibration Trigger Common
A30
Calibration Trigger Input
A31
Calibration Trigger Supply
A32
Screen
A33
A34
A35
A5.6 Fuel Selection Inputs
The Model 4500 Mk III can be configured to measure dust using two sets of dust
parameters.
Connect volt-free contacts between A37 and A38 to Select Fuel 1.
Connect volt-free contacts between A41 and A42 to Select Fuel 2.
Make both connections to Select Fuel 3.
Terminal
Function
A36
Fuel Select 1 Common
A37
Fuel Select 1 Input
A38
Fuel Select 1 Supply
A39
Cable
Screen
A40
Fuel Select 2 Common
A41
Fuel Select 2 Input
A42
Fuel Select 2 Supply
A5.7 Additional Connections
Terminals 61, 62 and 62 may be used to connect the 4 to 20 mA signal from the
transceiver to the customer’s data acquisition system.
Terminal
Function
Colour
61
4 to 20 mA +
Yellow
62
4 to 20 mA -
Green
63
Screen
Braided
Screen
Summary of Contents for 4500 MKIII
Page 4: ...Opacity and Dust Monitor User Guide Model 4500 MkIII Preface Blank...
Page 6: ...INTRODUCTION A...
Page 29: ...A 23 Model 4500 MkIII Opacity and Dust Monitor User Guide A4 3 Mounting the AFU APS I O...
Page 41: ...GETTING STARTED B...
Page 42: ...Opacity and Dust Monitor User Guide Model 4500 MkIII Preface Blank...
Page 76: ...THEORY OF OPERATION AND APPLICATION C...
Page 86: ...SYSTEM SPECIFICATION D...
Page 91: ...MAINTENANCE E...
Page 108: ...CHANGING THE INSTALLATION PATHLENGTH F...
Page 113: ...INSTRUMENT RECORD SHEETS G...
Page 114: ...Blank...
Page 117: ...OPTIONAL I O MODULES FOR AFU H...
Page 118: ...Blank...
Page 124: ...LONG PATHLENGTH OPTION App 1...
Page 126: ...Opacity and Dust Monitor User Guide Model 4500 MkIII App 1 2...