Rockwell Automation Publication 1560F-UM001A-EN-P - June 2019
227
Parameter Information
Appendix A
309
Input Status
0/65535
0
Input 1
Input 2
Input 7-1
Input 7-2
Input 7-3
Input 7-4
Input 8-1
Input 8-2
Input 8-3
Input 8-4
Input 9-1
Input 9-2
Input 9-3
Input 9-4
Displays the status of all the digital inputs for the SMC-50
Bit 0
- Displays status of control module input #1;
Bit 1
- Displays status of Control Module Input #2.
Bit 2
- Displays status of Control Module Port 7, 150-SM4
Option Module Input #1.
Bit 3
- Displays status of Control Module Port 7, 150-SM4
Option Module Input #2.
Bit 4
- Displays status of Control Module Port 7, 150-SM4 Option
Module Input #3.
Bit 5
- Displays status of Control Module Port 7, 150-SM4 Option
Module Input #4.
Bit 6
- Displays status of Control Module Port 8, 150-SM4
Option Module Input #1.
Bit 7
- Displays status of Control Module Port 8, 150-SM4 Option
Module Input #2.
Bit 8
- Displays status of Control Module Port 8, 150-SM4 Option
Module Input #3.
Bit 9
- Displays status of Control Module Port 8, 150-SM4 Option
Module Input #4.
Bit 10
- Displays status of Control Module Port 9, 150-SM4
Option Module Input #1.
Bit 11
- Displays status of Control Module Port 9, 150-SM4
Option Module Input #2.
Bit 12
- Displays status of Control Module Port 9, 150-SM4
Option Module Input #3.
Bit 13
- Displays status of Control Module Port 9, 150-SM4
Option Module Input #4.
Bit 14 & 15
- Reserved.
R
310
Locked Rotor A Lvl
%FLC
400/1000
600
Enables the user to enter a value for the Locked Rotor Alarm
Level (Locked Rtr A Lvl). The locked rotor value represents the
motor peak phase current to the load that if exceeded for the
period defined in Locked Rtr A Delay will signal a fault. The
Locked Rotor bit in the Motor Alarm En parameter must be set
to signal a alarm.
R/W
311
Locked Rotor A Dly
Secs
0.1/100
0.1
The time period that the peak phase current exceeds the Locked
Rtr F Level to signal a fault. The Locked Rotor bit in the Motor
Fault En parameter must be set to enable a fault.
R/W
Table 66 - SMC -50 Parameter List (Continued)
Number
Name
Unit
Min/Max
Default
Enum Text
Description
R/W
Summary of Contents for SMC-50
Page 10: ...10 Rockwell Automation Publication 1560F UM001A EN P June 2019 Table of Contents Notes ...
Page 12: ...12 Rockwell Automation Publication 1560F UM001A EN P June 2019 Preface Notes ...
Page 68: ...68 Rockwell Automation Publication 1560F UM001A EN P June 2019 Chapter 2 Installation Notes ...
Page 120: ...120 Rockwell Automation Publication 1560F UM001A EN P June 2019 Chapter 4 Programming Notes ...
Page 130: ...130 Rockwell Automation Publication 1560F UM001A EN P June 2019 Chapter 5 Metering Notes ...
Page 156: ...156 Rockwell Automation Publication 1560F UM001A EN P June 2019 Chapter 8 Diagnostics Notes ...
Page 198: ...198 Rockwell Automation Publication 1560F UM001A EN P June 2019 Chapter 10 Maintenance Notes ...
Page 284: ...284 Rockwell Automation Publication 1560F UM001A EN P June 2019 Appendix H Spare Parts Notes ...
Page 286: ...286 Rockwell Automation Publication 1560F UM001A EN P June 2019 Appendix I Accessories Notes ...
Page 291: ......