222
Rockwell Automation Publication 1560F-UM001A-EN-P - June 2019
Appendix A
Parameter Information
246
MVA Un A Lvl
MVA
0/1000
0.00
Allows the user to enter a value for the MVA Under Alarm Level
(MVA Un A Lvl). If the current actual value of the Apparent
Power (MVA) is less than the MVA Un A Lvl for a time period
greater than that defined by MVA Un A Dly, a MVA Un Alarm will
be signaled.
R/W
247
MVA Un A Dly
Secs
0.1/99
0.1
Allows the user to enter a time value for the Apparent Power
Under Alarm Delay (MVA Un A Dly). If the current actual value of
the Apparent Power (MVA) is less than the MVA Un A Lvl for a
time period greater than that defined by MVA Un A Dly, a MVA
Un Alarm will be signaled.
R/W
248
Lead PF Ov F Lvl
0/1
0.00
Allows the user to enter a value for the Leading Power Factor
Over Fault Level (Lead PF Ov F Lvl). If the current actual Power
Factor value is leading more than the Lead PF Ov F Lvl for a time
period greater than that defined by Lead PF Ov F Dly, a Lead PD
Ov Fault will be signaled.
R/W
249
Lead PF Ov F Dly
Secs
0.1/99
0.1
Allows the user to enter a time value for the Leading Power
Factor Over Fault Delay (Lead PF Ov F Dly). If the current actual
Power Factor value is leading more than the Lead PF Ov F Lvl for
a period greater than that defined by Lead PF Ov F Dly, a Lead
PD Ov fault will be signaled.
R/W
250
Lead PF Ov A Lvl
0/1
0.00
Allows the user to enter a value for the Leading Power Factor
Over Alarm Level (Lead PF Ov A Lvl). If the current actual Power
Factor value is leading more than the Lead PF Ov A Lvl for a
period greater than that defined by Lead PF Ov A Dly, a Lead PD
Ov alarm will be signaled.
R/W
251
Lead PF Ov A Dly
Secs
0.1/99
0.1
Allows the user to enter a time value for the Leading Power
Factor Over Alarm Delay (Lead PF Ov A Dly). If the current actual
Power Factor value is leading more than the Lead PF Ov A Lvl for
a period greater than that defined by Lead PF Ov A Dly, a Lead
PD Ov alarm will be signaled.
R/W
252
Lead PF Un F Lvl
0/1
0.00
Allows the user to enter a value for the Leading Power Factor
Under Fault Level (Lead PF Un F Lvl). If the current actual Power
Factor value is leading less than the Lead PF Un A Lvl for a time
period greater than that defined by Lead PF Un A Dly, a Lead PD
Un Fault will be signaled.
R/W
253
Lead PF Un F Dly
Secs
0.1/99
0.1
Allows the user to enter a time value for the Leading Power
Factor Under Fault Delay (Lead PF Un F Dly). If the current actual
Power Factor value is leading less than the Lead PF Un A Lvl for a
time period greater than that defined by Lead PF Un A Dly, a
Lead PD Un Fault will be signaled.
R/W
254
Lead PF Un A Lvl
0/1
0.00
Allows the user to enter a value for the Leading Power Factor
Under Alarm Level (Lead PF Un A Lvl). If the current actual
Power Factor value is leading less than the Lead PF Un A Lvl for a
time period greater than that defined by Lead PF Un A Dly, a
Lead PD Un Alarm will be signaled.
R/W
255
Lead PF Un A Dly
Secs
0.1/99
0.1
Allows the user to enter a time value for the Leading Power
Factor Under Alarm Delay (Lead PF Un A Dly). If the current
actual Power Factor value is leading less than the Lead PF Un A
Lvl for a time period greater than that defined by Lead PF Un A
Dly, a Lead PD Un Alarm will be signaled.
R/W
Table 66 - SMC -50 Parameter List (Continued)
Number
Name
Unit
Min/Max
Default
Enum Text
Description
R/W
Summary of Contents for SMC-50
Page 10: ...10 Rockwell Automation Publication 1560F UM001A EN P June 2019 Table of Contents Notes ...
Page 12: ...12 Rockwell Automation Publication 1560F UM001A EN P June 2019 Preface Notes ...
Page 68: ...68 Rockwell Automation Publication 1560F UM001A EN P June 2019 Chapter 2 Installation Notes ...
Page 120: ...120 Rockwell Automation Publication 1560F UM001A EN P June 2019 Chapter 4 Programming Notes ...
Page 130: ...130 Rockwell Automation Publication 1560F UM001A EN P June 2019 Chapter 5 Metering Notes ...
Page 156: ...156 Rockwell Automation Publication 1560F UM001A EN P June 2019 Chapter 8 Diagnostics Notes ...
Page 198: ...198 Rockwell Automation Publication 1560F UM001A EN P June 2019 Chapter 10 Maintenance Notes ...
Page 284: ...284 Rockwell Automation Publication 1560F UM001A EN P June 2019 Appendix H Spare Parts Notes ...
Page 286: ...286 Rockwell Automation Publication 1560F UM001A EN P June 2019 Appendix I Accessories Notes ...
Page 291: ......