Rockwell Automation Publication 1560F-UM001A-EN-P - June 2019
Appendix A
Parameter Information
Table 67 - 150-SM2 Option Card Parameters
Number
Name
Unit
Min/Max
Default
Enum Text
Description
Read/
Write
SM2.01
(GF)
Module Status
0/7
7
[Ready]
[PTC]
[CT Loss]
Displays information about the operational status of the 150-
SM2 PTC, Ground Fault, and External Current Transformer (CT)
Option Module.
Ready
: Bit 0 = Ready; Bit Set =1 indicates the module is ready
for operation.
PTC
: Bit 1 = PTC; 1 = PTC Indicating Fault 0; = No fault
CT Loss
: Bit 2 = CT Loss; 1 = CT disconnected; 0 = CT
Connected
R
SM2.02
(GF)
Fault Enable
0/3
0
PTC
Ground Fault
PTC
: 0 = PTC Fault Disabled; 1 = PTC Fault Enabled
GF
: 0 = Ground Fault Disabled; 1 = Ground Fault Enabled
R/W
SM2.02
(GF)
Fault Enable
(Refer to SM2.2)
SM2.03
(GF)
Alarm Enable
0/3
0
PTC
Ground Fault
PTC
: 0 = PTC Alarm Disabled; 1 = PTC Alarm Enabled
GF
: 0 = Ground Fault Alarm Disabled; 1 = Ground Fault Alarm
Enabled
R/W
SM2.04
(GF)
Restart Enable
0/3
0
PTC
Ground Fault
PTC
: 0 = does not restart after PTC Fault is cleared; 1 = restart
after PTC Fault is cleared
GF
: 0 = does not restart after the Ground Fault is cleared; 1 =
restart after the Ground Fault is cleared
R/W
SM2.05
(GF)
Turns Ratio
:1
100/2000
1000
Enables user to configure the turns ratio for the GFCT being
used.
R/W
SM2.06
(GF)
Gnd Flt Level
Amps
0/5
2.50
Enables the user to configure the level (value) of ground current
(primary current of GFCT) that determines a ground fault
condition.
R/W
SM2.07
(GF)
Gnd Flt Delay
Secs
0.1/250
0.5
Sets the time limit that the ground fault level must be exceeded
before signalling a fault.
R/W
SM2.08
(GF)
Gnd Flt A Level
Amps
0/5
2.50
Sets the level of ground current that determines a ground fault
alarm condition.
R/W
SM2.09
(GF)
Gnd Flt A Delay
Secs
0.1/250
0.5
Sets the time limit that the ground fault level must be exceeded
before signalling an alarm.
R/W
SM2.10
(GF)
Gnd Flt Inh Time
Secs
0/250
10.00
User configurable time delay to inhibit ground fault after a
start.
R/W
SM2.11
(GF)
Ground Current
Amps
0/5
0.00
Measured ground current.
R/W
SM2.12
(GF)
CT Enable
0/1
0
[Disable]
Enable
Disable/Enable CT Function.
R/W
SM2.13
(GF)
CT Scaling A
0/5
0.01
Displayed result of the SMC-50 tuning feature determination of
the scaling between external CT and the internal current
measuring circuitry.
R
SM2.14
(GF)
CT Scaling B
0/5
0.01
Displayed result of the SMC-50 tuning feature determination of
the scaling between external CT and the internal current
measuring circuitry.
R
SM2.15
(GF)
CT Scaling C
0/5
0.01
Displayed result of the SMC-50 tuning feature determination of
the scaling between external CT and the internal current
measuring circuitry.
R
Summary of Contents for SMC-50
Page 10: ...10 Rockwell Automation Publication 1560F UM001A EN P June 2019 Table of Contents Notes ...
Page 12: ...12 Rockwell Automation Publication 1560F UM001A EN P June 2019 Preface Notes ...
Page 68: ...68 Rockwell Automation Publication 1560F UM001A EN P June 2019 Chapter 2 Installation Notes ...
Page 120: ...120 Rockwell Automation Publication 1560F UM001A EN P June 2019 Chapter 4 Programming Notes ...
Page 130: ...130 Rockwell Automation Publication 1560F UM001A EN P June 2019 Chapter 5 Metering Notes ...
Page 156: ...156 Rockwell Automation Publication 1560F UM001A EN P June 2019 Chapter 8 Diagnostics Notes ...
Page 198: ...198 Rockwell Automation Publication 1560F UM001A EN P June 2019 Chapter 10 Maintenance Notes ...
Page 284: ...284 Rockwell Automation Publication 1560F UM001A EN P June 2019 Appendix H Spare Parts Notes ...
Page 286: ...286 Rockwell Automation Publication 1560F UM001A EN P June 2019 Appendix I Accessories Notes ...
Page 291: ......