228
Rockwell Automation Publication 1560F-UM001A-EN-P - June 2019
Appendix A
Parameter Information
312
Product Command
0/65535
0
Stop
Start
Jog
Clear Fault
Reserved
Emer Run
Reserved
Reserved
Reserved
Reserved
Rserved
Aux Enable
Network_1
Network_2
Network_3
Network_4
Displays an image of the DPI product command required for DPI
communications.
Stop
: 1 - Coast/Inhibit; 0 - No Action;
Start
: 1 - Start; 0 - No Action;
Jog
: 1 -Stop Maneuver/Inhibit; 0 -No Action;
Clear Fault
: 1 -Clear Faults; 0 - No Action;
Emer Run
: 1 - Enable Emergency Run Mode; 0 - Disable
Emergency Run Mode;
Aux Enable
: 1 -Use the Network #1 - #4 bits; 0 -Ignore the
Network #1 - #4 bits;
Network_1
: 1 -Closes any Output Configured for "Network 1";
0 - Opens any Output Configured for "Network 1";
Network_2
: 1 -Closes any Output Configured for "Network 2";
0 - Opens any Output Configured for "Network 2";
Network_3
: 1 -Closes any Output Configured for "Network 3";
0 - Opens any Output Configured for "Network 3";
Network_4
: 1 -Closes any Output Configured for "Network 4";
0 - Opens any Output Configured for "Network 4";
R
313
Rebalance Level
%
0/100
0
The percentage of motor current imbalance above which the
SMC-50 will rebalance the motor current
R/W
314
Va Peak
Volts
0/15000
0
The peak value of the Phase A line to neutral voltage during the
motor start, run, and stop cycle. The value resets to 0 when the
motor starts.
R
315
Vb Peak
Volts
0/15000
0
The peak value of the Phase B line to neutral voltage during the
motor start, run, and stop cycle.The value resets to 0 when the
motor starts.
R
316
Vc Peak
Volts
0/15000
0
The peak value of the Phase C line to neutral voltage during the
motor start, run, and stop cycle. The value resets to 0 when the
motor starts.
R
317
Ia Peak
Amps
0/15000
0
The peak value of the Phase A current during the motor start,
run, and stop cycle. The value resets to 0 when the motor starts.
R
318
Ib Peak
Amps
0/15000
0
The peak value of the Phase B current during the motor start,
run, and stop cycle. The value resets to 0 when the motor starts.
R
319
Ic Peak
Amps
0/15000
0
The peak value of the Phase C current during the motor start,
run, and stop cycle. The value resets to 0 when the motor starts.
R
320
SSVolts Phas A-B
Volts
0/15000
0
Snapshot of the Phase A-B voltage when a fault occurs. The
value is overwritten if a subsequent fault occurs
R
321
SSVolts Phas B-C
Volts
0/15000
0
Snapshot of the Phase B-C voltage when a fault occurs. The
value is overwritten if a subsequent fault occurs.
R
322
SSVolts Phas C-A
Volts
0/15000
0
Snapshot of the Phase C-A voltage when a fault occurs. The
value is overwritten if a subsequent fault occurs.
R
323
SSCurrent Phas A
Amps
0/15000
0
Snapshot of the Phase A current when a fault occurs. The value
is overwritten if a subsequent fault occurs.
R
324
SSCurrent Phas B
Amps
0/15000
0
Snapshot of the Phase B current when a fault occurs. The value
is overwritten if a subsequent fault occurs.
R
Table 66 - SMC -50 Parameter List (Continued)
Number
Name
Unit
Min/Max
Default
Enum Text
Description
R/W
Summary of Contents for SMC-50
Page 10: ...10 Rockwell Automation Publication 1560F UM001A EN P June 2019 Table of Contents Notes ...
Page 12: ...12 Rockwell Automation Publication 1560F UM001A EN P June 2019 Preface Notes ...
Page 68: ...68 Rockwell Automation Publication 1560F UM001A EN P June 2019 Chapter 2 Installation Notes ...
Page 120: ...120 Rockwell Automation Publication 1560F UM001A EN P June 2019 Chapter 4 Programming Notes ...
Page 130: ...130 Rockwell Automation Publication 1560F UM001A EN P June 2019 Chapter 5 Metering Notes ...
Page 156: ...156 Rockwell Automation Publication 1560F UM001A EN P June 2019 Chapter 8 Diagnostics Notes ...
Page 198: ...198 Rockwell Automation Publication 1560F UM001A EN P June 2019 Chapter 10 Maintenance Notes ...
Page 284: ...284 Rockwell Automation Publication 1560F UM001A EN P June 2019 Appendix H Spare Parts Notes ...
Page 286: ...286 Rockwell Automation Publication 1560F UM001A EN P June 2019 Appendix I Accessories Notes ...
Page 291: ......