Rockwell Automation Publication 1560F-UM001A-EN-P - June 2019
239
Parameter Information
Appendix A
SM4.14
(DIO)
Aux3 Config
0/12
0
[Normal]
UTS
Fault
Alarm
Ext Bypass
Ext Brake
DeviceLogix
Aux Conrol
Network 1
Network 2
Network 3
Network 4
Allows the user to configure the functionality of the Aux3 Relay
Output on the 150-SM4 Digital I/O Option Module.
[Normal]
: Aux3 closes when start command asserted and
opens when motor stops [Default].
UTS
: Aux3 closes when motor reaches up to speed and opens
when motor is not at speed.
Fault
: Aux3 closes when the SMC-50 enters a fault state and
opens when the fault is cleared.
Alarm
: Aux3 closes when the SMC-50 detects an alarm
condition and opens when alarm is
cleared.
Ext Bypass
: Aux3 closes when the SMC-50 enters the external
bypass mode and opens when it leaves that mode.
Ext Brake
: Aux3 closes when Ext Braking command is active
and opens when it is not active.
DeviceLogix: Aux3 is controlled by DeviceLogix program.
Aux Control
: When an auxiliary is configured for Aux Control, a
bit within the parameter Aux Control controls the state of that
auxiliary.
Network 1
: With an auxiliary configured as Network 1, it is
controlled over the Local Area Network (LAN) as Relay 1.
Network 2
: With an auxiliary configured as Network 2 it is
controlled over the LAN as Relay 2.
Network 3
: With an auxiliary configured as Network 2 it is
controlled over the LAN as Relay 3.
Network 4
: With an auxiliary configured as Network 2 it is
controlled over the LAN as Relay 4.
R/W
SM4.15
(DIO)
Aux3 Invert
0/1
0
[Disable]
Enable
Enables the user to invert the logic of the Aux3 output. When
disabled, it is a normally open relay output contact when de-
energized. By enabling the invert function, the relay contact
becomes a normally closed contact when de-energized.
Disable
: Aux3 Relay Output is not inverted (N.O.).
Enable
: Aux3 Relay Output is inverted (N.C.)
R/W
SM4.16
(DIO)
Aux3 On Delay
Secs
0/10
0.0
A user-selected time delay in activating the Aux3 Relay Contact
can be programmed.
Note: when an aux relay is configured for External Bypass, that
delay is not applied to the relay output.
R/W
SM4.17
(DIO)
Aux3 Off Delay
Secs
0/10
0.0
A user-selected time delay in de-activating the Aux3 Relay
Contact can be programmed.
Note: when an aux relay is configured for External Bypass, that
delay is not applied to the relay output.
R/W
SM4.18
(DIO)
Parameter Mgmt
0/1
0
[Ready]
Factory Default
Allows the user to set all 150-SM4 Digital I/O Option Module
parameters to default values.
Ready
: Waiting for command to set defaults.
Factory Default
: Set all writable parameters to factory default
values.
R/W
Table 68 - 150-SM4 Parameters (Continued)
Number
Name
Unit
Min/Max
Default
Enum Text
Description
Read/
Write
Summary of Contents for SMC-50
Page 10: ...10 Rockwell Automation Publication 1560F UM001A EN P June 2019 Table of Contents Notes ...
Page 12: ...12 Rockwell Automation Publication 1560F UM001A EN P June 2019 Preface Notes ...
Page 68: ...68 Rockwell Automation Publication 1560F UM001A EN P June 2019 Chapter 2 Installation Notes ...
Page 120: ...120 Rockwell Automation Publication 1560F UM001A EN P June 2019 Chapter 4 Programming Notes ...
Page 130: ...130 Rockwell Automation Publication 1560F UM001A EN P June 2019 Chapter 5 Metering Notes ...
Page 156: ...156 Rockwell Automation Publication 1560F UM001A EN P June 2019 Chapter 8 Diagnostics Notes ...
Page 198: ...198 Rockwell Automation Publication 1560F UM001A EN P June 2019 Chapter 10 Maintenance Notes ...
Page 284: ...284 Rockwell Automation Publication 1560F UM001A EN P June 2019 Appendix H Spare Parts Notes ...
Page 286: ...286 Rockwell Automation Publication 1560F UM001A EN P June 2019 Appendix I Accessories Notes ...
Page 291: ......