Rockwell Automation Publication 1560F-UM001A-EN-P - June 2019
211
Parameter Information
Appendix A
149
Logic Mask Act
0/65535
0
Displays which DPI port the SMC-50 will accept a start
command from. It may be different from the Logic Mask set by
the local user if someone changes it over the network.
bit 1
= port 1 (on board HIM)
bit 2
= port 2 (DPI port on control module)
bit 3
= port 3 (DPI port on control module with splitter)
bit 4
= port 4 (Internal Comm module)
bit 5-15
= reserved
R
150
Write Mask Cfg
0/65535
7FFF
This bits in this parameter allow the user to enable (bit=1) or
disable (Bit=0) which DPI ports the SMC-50 will accept write
commands from. Only selected ports can modify parameters.
bit 1
= port 1 (on board HIM) [Default=1]
bit 2
= port 2 (DPI port on control module) [Default=1]
bit 3
= port 3 (DPI port on control module with splitter)
[Default=1]
bit 4
= port 4 (Internal Comm module) [Default=1]
bit 5-15
= reserved [Default=0]
R/W
151
Write Mask Act
0/65535
0
Displays which DPI ports the SMC will accept write commands
from that can change parameters. It may be different from the
Write Mask Cfg parameter setup by the local user if someone
changes it over the network.
bit 1
= port 1 (on board HIM)
bit 2
= port 2 (DPI port on control module)
bit 3
= port 3 (DPI port on control module with splitter)
bit 4
= port 4 (Internal Comm module)
bit 5-15
= reserved
R
152
Port Mask Act
0/65535
0
Displays which DPI ports are active on the control module and
will accept operational commands from.
bit 1
= port 1 (on board HIM)
bit 2
= port 2 (DPI port on control module)
bit 3
= port 3 (DPI port on control module with splitter)
bit 4
= port 4 (Internal Comm module)
bit 5-15
= reserved
R
153
Data In A1
0/159999
0
This is the a channel IN Datalink index, holding the parameter
number of the parameter that will be written to during Datalink
communications. A value of 0 indicates that it is disabled.
R/W
154
Data In A2
0/159999
0
This is the a channel IN Datalink index, holding the parameter
number of the parameter that will be written to during Datalink
communications. A value of 0 indicates that it is disabled.
R/W
155
Data In B1
0/159999
0
This is the a channel IN Datalink index, holding the parameter
number of the parameter that will be written to during Datalink
communications. A value of 0 indicates that it is disabled.
R/W
Table 66 - SMC -50 Parameter List (Continued)
Number
Name
Unit
Min/Max
Default
Enum Text
Description
R/W
Summary of Contents for SMC-50
Page 10: ...10 Rockwell Automation Publication 1560F UM001A EN P June 2019 Table of Contents Notes ...
Page 12: ...12 Rockwell Automation Publication 1560F UM001A EN P June 2019 Preface Notes ...
Page 68: ...68 Rockwell Automation Publication 1560F UM001A EN P June 2019 Chapter 2 Installation Notes ...
Page 120: ...120 Rockwell Automation Publication 1560F UM001A EN P June 2019 Chapter 4 Programming Notes ...
Page 130: ...130 Rockwell Automation Publication 1560F UM001A EN P June 2019 Chapter 5 Metering Notes ...
Page 156: ...156 Rockwell Automation Publication 1560F UM001A EN P June 2019 Chapter 8 Diagnostics Notes ...
Page 198: ...198 Rockwell Automation Publication 1560F UM001A EN P June 2019 Chapter 10 Maintenance Notes ...
Page 284: ...284 Rockwell Automation Publication 1560F UM001A EN P June 2019 Appendix H Spare Parts Notes ...
Page 286: ...286 Rockwell Automation Publication 1560F UM001A EN P June 2019 Appendix I Accessories Notes ...
Page 291: ......