Rockwell Automation Publication 1560F-UM001A-EN-P - June 2019
141
Communications
Chapter 7
Table 51 - Logic Command Word (Control)
Reference/Feedback
The SMC-50 control module does not offer the analog
Reference
feature. The
analog
Feedback
feature is supported and provides Current Average, Parameter
5, automatically as the feedback word.
Parameter Information
A complete listing of the SMC-50 parameters is located in
.
Scale Factors for PLC
Communication
The parameter values stored and produced by the SMC-50 through
communication are unscaled numbers. When reading or writing values from a
PLC image table, it is important to apply the proper scaling factor, which is based
on the number of decimal places.
Read Example
Power Factor, Parameter 17—
The stored value is 85. Because this value has two
decimal places, the value should be divided by 100. The correctly read value is
0.85.
Write Example
Motor FLC, Parameter 78—
The example value, which is to be written to the
SMC-50 control module, is 75 A. Because this value has one decimal place, the
value should be multiplied by 10. The correctly written value is 750.
Bit
Number
Control
Description
1
0
0
Stop
Coast/Inhibit
No action
1
Start
Start
No action
2
Stop Option
Stop/Maneuver
No action
3
Clear Fault
Clear fault
No action
5
Emergency Run
Enable emergency run mode
Disable emergency run mode
8…10
Reserved
These bits must always be set to 0
11
Aux Enable
Use the Network #1 - #4 bits
Ignore the Network #1 - #4 bits
12
Network #1
Closes any output configured for
Network #1
Opens any output configured for
Network #1
13
Network #2
Closes any output configured for
Network #2
Opens any output configured for
Network #2
14
Network #3
Closes any output configured for
Network #3
Opens any output configured for
Network #3
15
Network #4
Closes any output configured for
Network #4
Opens any output configured for
Network #4
Summary of Contents for SMC-50
Page 10: ...10 Rockwell Automation Publication 1560F UM001A EN P June 2019 Table of Contents Notes ...
Page 12: ...12 Rockwell Automation Publication 1560F UM001A EN P June 2019 Preface Notes ...
Page 68: ...68 Rockwell Automation Publication 1560F UM001A EN P June 2019 Chapter 2 Installation Notes ...
Page 120: ...120 Rockwell Automation Publication 1560F UM001A EN P June 2019 Chapter 4 Programming Notes ...
Page 130: ...130 Rockwell Automation Publication 1560F UM001A EN P June 2019 Chapter 5 Metering Notes ...
Page 156: ...156 Rockwell Automation Publication 1560F UM001A EN P June 2019 Chapter 8 Diagnostics Notes ...
Page 198: ...198 Rockwell Automation Publication 1560F UM001A EN P June 2019 Chapter 10 Maintenance Notes ...
Page 284: ...284 Rockwell Automation Publication 1560F UM001A EN P June 2019 Appendix H Spare Parts Notes ...
Page 286: ...286 Rockwell Automation Publication 1560F UM001A EN P June 2019 Appendix I Accessories Notes ...
Page 291: ......