Parameter Information
Appendix A
125
THD I A Dly
Secs
0.1/99
0.1
The time period that the average THD on the phase current
exceeds the THD I A Lvl to signal an alarm. The THD I bit in the
Motor Alarm En parameter must be set to signal an alarm.
R/W
126
PM Hours
Hrs
1/10000
10000
This is a counter the user can set to generate an alarm or fault to
signal a need for preventive maintenance. The Hours to PM
parameter is initialized to this value and counts down when the
motor is running.
R/W
127
PM Starts
1/50000
100
This is a counter the user can set to generate an alarm or fault to
signal a need for preventive maintenance. The Starts to PM
parameter is initialized to this value and counts down each time
the motor is started.
R/W
128
Starts per Hour
1/10
10
The user can program the maximum number of starts within a
sliding one-hour window. Once the number of starts per hour is
reached any additional starts will cause a fault.
R/W
129
Freq High F Lvl
Hz
45/66
63
The highest line voltage frequency that can be applied to the
SMC-50 before causing a Freq High F Lvl fault. The Freq High bit
in the Starter Fault En parameter must be set to signal a fault.
R/W
130
Freq Low F Lvl
Hz
45/66
47
The lowest line voltage frequency that can be applied to the
SMC-50 before causing a Freq Low F Lvl fault.The Freq Low bit in
the Starter Fault En parameter must be set to signal a fault.
R/W
131
Freq High A Lvl
Hz
45/66
63
The highest line voltage frequency that can be applied to the
SMC-50 before causing a Freq High F Lvl alarm. The Freq High
bit in the Starter Alarm parameter must be set to signal an
alarm.
R/W
132
Freq Low A Lvl
Hz
45/66
47
The lowest line voltage frequency that can be applied to the
SMC-50 before causing a Freq Low F Lvl alarm. The Freq Low bit
in the Starter Alarm parameter must be set to signal an alarm.
R/W
133
Restart Attempts
0/5
0
Allows the user to enable the SMC-50 to auto-restart for up-to
five attempts after a thyristor has failed to fire and results in an
open gate fault trip.
R/W
134
Restart Dly
Secs
0/60
0
Provides a delay time prior to the SMC-50’s attempt to restart
the motor after a fault.
R/W
135
Starts Restart En
Bit Value 0/1
0
Future
Volt Unbal
Overvoltage
Undervoltage
Phase Rev
Line Loss
Open Gate
Config Change
Freq
THD V
Future
Allows the user to select which type of fault that the SMC-50
can try to restart from once the restart delay period has expired.
To enable a restart from a fault, the function must be selected
(1). Restart Attempts, Parameter 133, and Restart Delay,
Parameter 134, must be configured.
R/W
Table 66 - SMC -50 Parameter List (Continued)
Number
Name
Unit
Min/Max
Default
Enum Text
Description
R/W
Summary of Contents for SMC-50
Page 10: ...10 Rockwell Automation Publication 1560F UM001A EN P June 2019 Table of Contents Notes ...
Page 12: ...12 Rockwell Automation Publication 1560F UM001A EN P June 2019 Preface Notes ...
Page 68: ...68 Rockwell Automation Publication 1560F UM001A EN P June 2019 Chapter 2 Installation Notes ...
Page 120: ...120 Rockwell Automation Publication 1560F UM001A EN P June 2019 Chapter 4 Programming Notes ...
Page 130: ...130 Rockwell Automation Publication 1560F UM001A EN P June 2019 Chapter 5 Metering Notes ...
Page 156: ...156 Rockwell Automation Publication 1560F UM001A EN P June 2019 Chapter 8 Diagnostics Notes ...
Page 198: ...198 Rockwell Automation Publication 1560F UM001A EN P June 2019 Chapter 10 Maintenance Notes ...
Page 284: ...284 Rockwell Automation Publication 1560F UM001A EN P June 2019 Appendix H Spare Parts Notes ...
Page 286: ...286 Rockwell Automation Publication 1560F UM001A EN P June 2019 Appendix I Accessories Notes ...
Page 291: ......