Rockwell Automation Publication 1560F-UM001A-EN-P - June 2019
253
ArcShield Unit Information
Appendix D
Figure 78 - Cross-section of plenum extension, dimensions in mm [inches]
Plenum Exhaust
Considerations
The following options for locating the plenum exhaust are presented:
1.
Plenum ducted to an area of the control room where arc gases are
permitted to escape, with plenum extensions (see
Figure 79
,
Figure 80
and
Figure 81
).
2.
Plenum duct to outside of control room (see
Figure 79
and
Figure 80
).
Plan the location where the plenum will exhaust. Ensure that:
• There is no access to personnel while equipment is energized.
• Area is free of flammable material or vapors
Ensure that adequate space is provided around the plenum exhaust, as outlined in
Figure 79
through
Figure 81
.
633 [25]
584 [23]
IMPORTANT
Be aware that equipment in the area of the plenum exhaust point will be
damaged or destroyed.
Summary of Contents for SMC-50
Page 10: ...10 Rockwell Automation Publication 1560F UM001A EN P June 2019 Table of Contents Notes ...
Page 12: ...12 Rockwell Automation Publication 1560F UM001A EN P June 2019 Preface Notes ...
Page 68: ...68 Rockwell Automation Publication 1560F UM001A EN P June 2019 Chapter 2 Installation Notes ...
Page 120: ...120 Rockwell Automation Publication 1560F UM001A EN P June 2019 Chapter 4 Programming Notes ...
Page 130: ...130 Rockwell Automation Publication 1560F UM001A EN P June 2019 Chapter 5 Metering Notes ...
Page 156: ...156 Rockwell Automation Publication 1560F UM001A EN P June 2019 Chapter 8 Diagnostics Notes ...
Page 198: ...198 Rockwell Automation Publication 1560F UM001A EN P June 2019 Chapter 10 Maintenance Notes ...
Page 284: ...284 Rockwell Automation Publication 1560F UM001A EN P June 2019 Appendix H Spare Parts Notes ...
Page 286: ...286 Rockwell Automation Publication 1560F UM001A EN P June 2019 Appendix I Accessories Notes ...
Page 291: ......