218
Rockwell Automation Publication 1560F-UM001A-EN-P - June 2019
Appendix A
Parameter Information
215
Phase Shift 100
-360/360
0
Timing parameters used in speed measurement algorithms.
These parameters are not typically modified and it is
recommended that RA Technical Support be contacted for
assistance before attempting to do so.
R/W
216
Board Temp
o
C
-25/100
20
Displays the internal temperature of the SMC control module.
R
217
Exp 7 Config
0/5
0
[None]
Input/Output
Analog I/O
(future)
GFCT/PTC/CT
DIP Switch
Seq Start
(future)
Displays the type of expansion board plugged into Expansion
Port 7.
R
218
Exp 8 Config
0/5
0
[None]
Input/Output
Analog I/O
(future)
GFCT/PTC/CT
DIP Switch
Seq Start
(future)
Displays the type of expansion board plugged into Expansion
Port 8.
R
219
Exp 9 Config
0/5
0
[None]
Input/Output
Analog I/O
(future)
GFCT/PTC/CT
DIP Switch
Seq Start
(future)
Displays the type of expansion board plugged into Expansion
Port 9.
R
224
Line Frequency
Hz
0/100
0
Displays the line frequency of the three phase voltage applied
to the SMC-50 at terminals L1, L2, and L3.
R
225
Freq High F Dly
Secs
0.1/99
0.1
Allows the user to configure the time period that the supplied
line voltage frequency must exceed Freq High F Lvl parameter
value before causing a Freq High fault. The Freq High bit must
be set in the Starter Fault En parameter for the fault to activate.
R
226
Freq High A Dly
Secs
0.1/99
0.1
Allows the user to configure the time period that the supplied
line voltage frequency must exceed Freq High A Lvl parameter
value before causing a Freq High alarm. The Freq High bit must
be set in the Starter Alarm parameter for the fault to activate.
R
227
Freq Low F Dly
Secs
0.1/99
0.1
Allows the user to configure the time period that the supplied
line voltage frequency must drop below Freq Low F Lvl
parameter value before causing a Freq Low fault. The Freq Low
bit must be set in the Starter Fault En parameter for the fault to
activate.
R
Table 66 - SMC -50 Parameter List (Continued)
Number
Name
Unit
Min/Max
Default
Enum Text
Description
R/W
Summary of Contents for SMC-50
Page 10: ...10 Rockwell Automation Publication 1560F UM001A EN P June 2019 Table of Contents Notes ...
Page 12: ...12 Rockwell Automation Publication 1560F UM001A EN P June 2019 Preface Notes ...
Page 68: ...68 Rockwell Automation Publication 1560F UM001A EN P June 2019 Chapter 2 Installation Notes ...
Page 120: ...120 Rockwell Automation Publication 1560F UM001A EN P June 2019 Chapter 4 Programming Notes ...
Page 130: ...130 Rockwell Automation Publication 1560F UM001A EN P June 2019 Chapter 5 Metering Notes ...
Page 156: ...156 Rockwell Automation Publication 1560F UM001A EN P June 2019 Chapter 8 Diagnostics Notes ...
Page 198: ...198 Rockwell Automation Publication 1560F UM001A EN P June 2019 Chapter 10 Maintenance Notes ...
Page 284: ...284 Rockwell Automation Publication 1560F UM001A EN P June 2019 Appendix H Spare Parts Notes ...
Page 286: ...286 Rockwell Automation Publication 1560F UM001A EN P June 2019 Appendix I Accessories Notes ...
Page 291: ......