226
Rockwell Automation Publication 1560F-UM001A-EN-P - June 2019
Appendix A
Parameter Information
298
-MVAR Ov F Dly
Secs
0.1/99
0.1
Enables the user to enter a time value for the Generated
Reactive Power Over Fault Delay (-MVAR Ov F Dly). If the current
actual value for the Generated Reactive Power is more than the
-MVAR Ov F Lvl for a time period greater than that defined by -
MVAR Ov F Dly, a -MVAR Ov fault will be signaled.
R/W
299
-MVAR Ov A Lvl
MVAR
-1000/0
0.000
Enables the user to enter a value for the Generated Reactive
Power Over Alarm Level (-MVAR Ov A Lvl). If the current actual
value for Generated Reactive Power is more than the -MVAR Ov
A Lvl for a period greater than that defined by -MVAR Ov A Dly, a
-MVAR Ov Alarm will be signaled.
R/W
300
-MVAR Ov A Dly
Secs
0.1/99
0.1
Enables the user to enter a time value for the Generated
Reactive Power Over Alarm Delay (-MVAR Ov A Dly). If the
current actual value for the Generated Reactive Power is more
than the -MVAR Ov A Lvl for a period greater than that defined
by -MVAR Ov A Dly, a -MVAR Ov alarm will be signaled.
R/W
301
-MVAR Un F Lvl
MVAR
-1000/0
0.000
Enables the user to enter a value for the Generated Reactive
Power Under Fault Level (-MVAR Un F Lvl). If the current actual
value for Generated Reactive Power is less than the -MVAR Un F
Lvl for a period greater than that defined by -MVAR Un F Dly, a -
MVAR Un Fault will be signaled.
R/W
302
-MVAR Un F Dly
Secs
0.1/99
0.1
Enables the user to enter a time value for the Generated
Reactive Power Under Fault Delay (-MVAR Un F Dly). If the
current actual value for Generated Reactive Power is less than
the -MVAR Un F Lvl for a period greater than that defined by -
MVAR Un F Dly, a -MVAR Un Fault will be signaled.
R/W
303
-MVAR Un A Lvl
MVAR
-1000/0
0.000
Enables the user to enter a value for the Generated Reactive
Power Under Alarm Level (-MVAR Un A Lvl). If the current actual
value for Generated Reactive Power is less than the -MVAR Un A
Lvl for a period greater than that defined by -MVAR Un A Dly, a
MVAR Un Alarm will be signaled.
R/W
304
-MVAR Un A Dly
Secs
0.1/99
0.1
Enables the user to enter a time value for the Generated
Reactive Power Under Alarm Delay (-MVAR Un A Dly). If the
current actual value for Generated Reactive Power is less than
the -MVAR Un A Lvl for a period greater than that defined by -
MVAR Un A Dly, a -MVAR Un Alarm will be signaled.
R/W
305
Starting Torque
%
0/300
100
Enables the user to enter Starting Torque value required for a
torque start operation.
R/W
306
Starting Torque 2
%
0/300
100
Enables the user to enter an alternate Starting Torque required
for a torque start operation.
R/W
Table 66 - SMC -50 Parameter List (Continued)
Number
Name
Unit
Min/Max
Default
Enum Text
Description
R/W
Summary of Contents for SMC-50
Page 10: ...10 Rockwell Automation Publication 1560F UM001A EN P June 2019 Table of Contents Notes ...
Page 12: ...12 Rockwell Automation Publication 1560F UM001A EN P June 2019 Preface Notes ...
Page 68: ...68 Rockwell Automation Publication 1560F UM001A EN P June 2019 Chapter 2 Installation Notes ...
Page 120: ...120 Rockwell Automation Publication 1560F UM001A EN P June 2019 Chapter 4 Programming Notes ...
Page 130: ...130 Rockwell Automation Publication 1560F UM001A EN P June 2019 Chapter 5 Metering Notes ...
Page 156: ...156 Rockwell Automation Publication 1560F UM001A EN P June 2019 Chapter 8 Diagnostics Notes ...
Page 198: ...198 Rockwell Automation Publication 1560F UM001A EN P June 2019 Chapter 10 Maintenance Notes ...
Page 284: ...284 Rockwell Automation Publication 1560F UM001A EN P June 2019 Appendix H Spare Parts Notes ...
Page 286: ...286 Rockwell Automation Publication 1560F UM001A EN P June 2019 Appendix I Accessories Notes ...
Page 291: ......