162
Rockwell Automation Publication 1560F-UM001A-EN-P - June 2019
Chapter 9
Troubleshooting
Table 59 - Motor Will Not Start—No Output Voltage to the Motor
Table 60 - Motor Rotates but Does Not Accelerate to Full Speed
Locked Rotor
70
In All Modes
• Motor has stalled; rotor is not turning
• Check motor and load for binding or jammed conditions
• Parameters are not adequately configured for the application.
Review and adjust.
• Disable the fault/alarm feature.
Start
71
Starting
• A start event (command) has occurred. This is
not a fault.
• NA
Stop Option
73
Stop Option
• A stop option event (command) has occurred.
This is not a fault.
• NA
Coast
74
Coast
• A coast-to-stop event (command) has
occurred. This is not a fault.
• NA
Clear Fault
75
Faulted
• A clear fault event (command) has occurred.
This does not generate a fault.
• NA
Fault
76
Faulted
• A fault event (command) has occurred. This is
not a fault.
• NA
Param Change
77
Stopped
• A change to one of the controller parameters
has occurred. This is not a fault.
• NA
Reserved
78…99
NA
• NA
• NA
System Faults
100…199
In All Modes
• There is an issue with the control module
wiring
• The control module is defective
• Review the control module wiring. Ensure the ground terminal is
secure and connected to the system’s earth ground. Ensure an RC
snubber/suppressor is connected to all inductive loads in the
control circuit. See input wiring.
• Replace the control module.
(1) The Real, Reactive, and Apparent Power faults/alarms are best suited to provide indication of an abnormal running operation of the motor or system which another parameter (for example,
Underload, Overload, Jam, Stall, etc.) does not provide. To understand what is an abnormal running operation, you need to determine a "normal" or "typical" value, usually established during system
startup.
(2) "X" indicates a port number in which the expansion module resides in the SMC-50 control module .
(3) If controller based motor overload is disabled, external motor overload protection should be used.
Table 58 - Fault Display Explanation (Continued)
Display
Fault Code
Fault Enabled
Possible Causes
Possible Solutions
Display
Possible Cause
Possible Solutions
Fault displayed
• See fault description
• See
Table 58
addressing fault conditions
HIM display is blank
• Failed HIM
• Control voltage is absent
• Failed control module
• HIM connection is loose
• Check control wiring and correct if necessary
• Check HIM connection
• Cycle control power
• Replace HIM only
• Replace control module only
Stopped
0.0 Amps
• Pilot devices
• SMC Enable input is open at terminal 9
• Configured or wired input terminals are not
wired correctly
• Start-Stop control has not been enabled for
the human interface module
• Control voltage
• Failed control module
• Check wiring; follow the instructions on
• Check control voltage
• Replace control module
Starting
• One or more power phases are missing
• Isolation contactor (if used) is not picking up
• Check power system
• Check that the controller Aux. relay output
controlling the Isolation Contactor is
configured to "Normal".
• Check the Isolation Contactor for proper
operation
Display
Possible Cause
Possible Solutions
Fault displayed
• See fault description
• See
Table 58
addressing fault conditions
Starting
• Mechanical problems
Inadequate Current Limit setting
• Failed control module
• Check for binding or external loading and correct
• Check motor
• Adjust the Current Limit Level to a higher setting
• Replace control module
Summary of Contents for SMC-50
Page 10: ...10 Rockwell Automation Publication 1560F UM001A EN P June 2019 Table of Contents Notes ...
Page 12: ...12 Rockwell Automation Publication 1560F UM001A EN P June 2019 Preface Notes ...
Page 68: ...68 Rockwell Automation Publication 1560F UM001A EN P June 2019 Chapter 2 Installation Notes ...
Page 120: ...120 Rockwell Automation Publication 1560F UM001A EN P June 2019 Chapter 4 Programming Notes ...
Page 130: ...130 Rockwell Automation Publication 1560F UM001A EN P June 2019 Chapter 5 Metering Notes ...
Page 156: ...156 Rockwell Automation Publication 1560F UM001A EN P June 2019 Chapter 8 Diagnostics Notes ...
Page 198: ...198 Rockwell Automation Publication 1560F UM001A EN P June 2019 Chapter 10 Maintenance Notes ...
Page 284: ...284 Rockwell Automation Publication 1560F UM001A EN P June 2019 Appendix H Spare Parts Notes ...
Page 286: ...286 Rockwell Automation Publication 1560F UM001A EN P June 2019 Appendix I Accessories Notes ...
Page 291: ......