Publication 1747-6.5.5 - August 2000
6-8
Creating and Running the Example Application Program
Downloading and Running the Program via a DH+ Network
Follow the procedure below to download and run the example
program via a DH+ network.
1.
Click on the
Comms
menu in RSLogix 500 and select
System
Communications
.
RSLinx
will start, and the
Communications
window will open.
2.
Select your Data Highway Plus driver (
AB_KT-1, Data Highway
Plus
in the above example).
3.
Select the “+” next to your Data Highway Plus driver (
AB_KT-1
above) to expand the tree.
4.
Highlight the SLC 500 processor and click on the
Download
button.
5.
After the download is complete, go
Online
and put the SLC 500
processor in
Run
mode.
IMPORTANT
You must also place the 1747-SDN scanner in run
mode by setting the Run bit (bit 0) in the scanner’s
command register. The command register is located
at word 0 in the Output image table.
Summary of Contents for SLC 500 DeviceNet
Page 1: ...SLC 500 DeviceNet Scanner Module 1747 SDN User Manual...
Page 4: ......
Page 52: ...Publication 1747 6 5 5 August 2000 3 16 Hardware Setup...
Page 68: ...Publication 1747 6 5 5 August 2000 4 16 Configuring the DeviceNet Network...
Page 86: ...Publication 1747 6 5 5 August 2000 5 18 Communicating with DeviceNet from Another Network...
Page 96: ...Publication 1747 6 5 5 August 2000 6 10 Creating and Running the Example Application Program...
Page 106: ...Publication 1747 6 5 5 August 2000 A 6 Data Map Example...
Page 118: ...Publication 1747 6 5 5 August 2000 E 4 Configuring SLC 5 05 Ethernet Communications...
Page 128: ...Publication 1747 6 5 5 August 2000 G 4 Installing and Configuring the DH Communications Driver...
Page 137: ......