B-2
Configuring the M0/M1 Files Using RSLogix 500
4.
Double-click on the
1747-SDN
module.
The
Advanced I/O Configuration
window will open.
5.
Set the
MO Length
and the
M1 Length
to 361 (or greater) as
shown above.
6.
Click on the
OK
button.
7. Download
the changes to the processor.
IMPORTANT
The SLC 500 must be placed in
Run
mode at least
one time after downloading the M0/M1configuration
to enable 1747-SDN pass-through transactions.