Publication 1747-6.5.5 - August 2000
Hardware Setup
3-5
Installing the ControlNet
RS-232 Interface Module
To communicate with the SLC 500 processor via a ControlNet network
you must install a 1747-KFC15 ControlNet RS-232 Interface module in
the 1746 I/O chassis close to the processor.
Configuring the 1747-KFC15 Module’s RS-232 Port
The RS-232 serial port on the 1747-KFC15 module is configured using
three banks (S1, S2, and S3) of DIP switches mounted on the module’s
printed circuit board.
For the example application, we used the following configuration to
match the configuration of the SLC 500 processor’s RS-232 port
described in the previous section:
IMPORTANT
The communication parameters of 1747-KFC15
module must match those of the SLC 500 processor.
Channel 0 Configuration
DF1 Station Address: 0
Diagnostic Command
Execution:
Disabled
Baud Rate:
19200
Duplicate Detect:
Enabled
Full/Half Duplex:
Full Duplex
Error Detect:
CRC
Parity:
NONE
Retries:
3
Handshake:
No Handshaking
DF1 ACK Timeout:
1.0 sec.
Note: The upper position as
shown above is ON. The lower
position is OFF.
Summary of Contents for SLC 500 DeviceNet
Page 1: ...SLC 500 DeviceNet Scanner Module 1747 SDN User Manual...
Page 4: ......
Page 52: ...Publication 1747 6 5 5 August 2000 3 16 Hardware Setup...
Page 68: ...Publication 1747 6 5 5 August 2000 4 16 Configuring the DeviceNet Network...
Page 86: ...Publication 1747 6 5 5 August 2000 5 18 Communicating with DeviceNet from Another Network...
Page 96: ...Publication 1747 6 5 5 August 2000 6 10 Creating and Running the Example Application Program...
Page 106: ...Publication 1747 6 5 5 August 2000 A 6 Data Map Example...
Page 118: ...Publication 1747 6 5 5 August 2000 E 4 Configuring SLC 5 05 Ethernet Communications...
Page 128: ...Publication 1747 6 5 5 August 2000 G 4 Installing and Configuring the DH Communications Driver...
Page 137: ......