Publication 1747-6.5.5 - August 2000
4-14
Configuring the DeviceNet Network
5.
Select the
Output
tab.
6.
In the
Memory
field, select
M File
.
7.
Highlight the RediSTATION and click on the
AutoMap
button.
In this example, the output to the RediSTATION appears in the M0
file for the device in slot 2 as word 0, bits 0 to 7
.
Recall from
chapter 3 that the indicator light is output bit 0. Therefore, the
address for the RediSTATION indicator light is:
M0:2.0.0
8. Note the address assigned to this output in your system.
You
will enter this address in the example ladder logic program in the
following chapter.
After mapping the
RediSTATION output
address will appear
here.