Publication 1747-6.5.5 - August 2000
4-12
Configuring the DeviceNet Network
2.
Make sure that the
Polled
box is checked and that the
Rx Size
and
Tx Size
are each 1 byte.
3.
Click on
OK
to close the
Edit I/O Parameters
window for the
RediSTATION.
4.
Click on
OK
again. You will be prompted to download the changes
to the 1747-SDN module.
5.
Click on
Yes
to download the new configuration.
AutoMapping the Devices into the Scanlist
Follow the procedure below to automatically map the photoeye and
RediSTATION to the SLC 500 processor.
1.
Double-click on the
1747-SDN
module icon and select the
Input
tab.
TIP
If you want to know how to map the devices
manually, click on the
Help
button at the bottom of
the screen and select “Map device input data
manually”.