Publication 1747-6.5.5 - August 2000
7-4
Troubleshooting
85
Run time data size returned from slave
device is not the size expected.
Check slave device installation and
configuration.
86
Device is producing idle state data
while the scanner is in Run Mode.
Check device configuration/slave node
status.
87
Available for allocation. Scanner has
not yet been detected by allocated
master, or slave mode is enabled but
scanner is not allocated to a master.
Monitor scanner to determine if error
code clears when master detects
scanner. If error remains, check scanner
slave mode configuration.
88
This is not an error. At power-up and
reset, the module displays all 14
segments of the node address and
status display LEDs.
None.
89
Auto Device Replacement (ADR) error.
Slave device responded with an error
to the initialization data sent to it by
the scanner; or the configuration table
in the scanner’s flash memory is not
valid for a slave node.
Try the ADR download again. If it still
fails, try clearing the ADR flash by
downloading an empty ADR
configuration to the scanner and then try
the ADR configuration again.
90
User has disabled communication port Reconfigure your module. Check the
disable bit in the Module Command
Register.
91
Bus-off condition detected on comm
port. Module is detecting
communication errors.
Check DeviceNet connections and
physical media integrity. Check system
for failed slave devices or other possible
sources of network interference.
92
No network power detected on comm
port.
Provide network power. Make sure that
module drop cable is providing network
power to module comm port.
95
Application FLASH update in progress. None. Do not disconnect the module
while application FLASH is in progress.
You will lose any existing data in the
module’s memory.
97
Module halted by user command.
None.
98
Unrecoverable firmware failure.
Service or replace your module.
99
Unrecoverable hardware failure.
Service or replace your module.
E9
Non-volatile configuration corrupt
Cycle power to module. Download
configuration to module
.
Table 7.C - Numeric Display Code Summary
Numeric
Code
Description
Take this action
Summary of Contents for SLC 500 DeviceNet
Page 1: ...SLC 500 DeviceNet Scanner Module 1747 SDN User Manual...
Page 4: ......
Page 52: ...Publication 1747 6 5 5 August 2000 3 16 Hardware Setup...
Page 68: ...Publication 1747 6 5 5 August 2000 4 16 Configuring the DeviceNet Network...
Page 86: ...Publication 1747 6 5 5 August 2000 5 18 Communicating with DeviceNet from Another Network...
Page 96: ...Publication 1747 6 5 5 August 2000 6 10 Creating and Running the Example Application Program...
Page 106: ...Publication 1747 6 5 5 August 2000 A 6 Data Map Example...
Page 118: ...Publication 1747 6 5 5 August 2000 E 4 Configuring SLC 5 05 Ethernet Communications...
Page 128: ...Publication 1747 6 5 5 August 2000 G 4 Installing and Configuring the DH Communications Driver...
Page 137: ......