Rockwell Automation Publication 1783-UM007I-EN-P - December 2017
39
Get Started
Chapter 2
4.
Click Submit.
The switch initializes its configuration for typical industrial
EtherNet/IP applications by running the global macro as described on
. You can then log on to Device Manager for further
configuration or exit the application.
5.
Turn off DC or AC power at the source, disconnect any cables to the
switch, and install the switch in your network.
6.
If you used single-mode Express Setup or multi-mode Express Setup in
Short Press mode, refresh the computer IP address:
•
For a dynamically assigned IP address, disconnect the computer from
the switch and reconnect the computer to the network. The network
DHCP server assigns a new IP address to the computer.
•
For a statically assigned IP address, change it to the previously
configured IP address.
7.
For Stratix 5400 and 5410 switches, synchronize the SD card that came
with the switch with the internal memory of the switch:
•
To synchronize the SD card via Device Manager, see
•
To synchronize the SD card via the Logix Designer application, see
After initial setup with Express Setup, you can change the settings if you want
to move the switch to another management VLAN or to another network. To
change Express Setup settings after initial setup, access the Express Setup page
from the Admin menu in Device Manager.
Telnet
Check Telnet to enable Telnet. You can use Telnet to access the switch via the command-line interface (CLI). For more information about the CLI,
see
. Telnet uses the local account user name and password.
IMPORTANT:
We recommend that you use SSH instead of Telnet for access to the switch. SSH provides more security for remote connections than
Telnet by providing strong encryption.
CIP and Enable Password,
Confirm Password
Enter the CIP and Enable password, or leave this field blank if you do not want to change the password. Renenter the password to confirm.
Same As Admin Password
Check Same As Admin Password to set the password that is used for CIP to the same user password specified under Network Settings.
Table 11 - Express Setup Mode Fields (Continued)
Field
Description
IMPORTANT
For 1783-BMS4S2SGL or 1783-BMS4S2SGA switches, make sure that
DC power is disconnected before disconnecting Ethernet cables.
Summary of Contents for armorstratix 5700
Page 10: ...10 Rockwell Automation Publication 1783 UM007I EN P December 2017 Table of Contents Notes ...
Page 12: ...12 Rockwell Automation Publication 1783 UM007I EN P December 2017 Preface Notes ...
Page 72: ...72 Rockwell Automation Publication 1783 UM007I EN P December 2017 Chapter 2 Get Started Notes ...
Page 396: ...396 Rockwell Automation Publication 1783 UM007I EN P December 2017 Appendix A DataTypes Notes ...
Page 457: ......