Rockwell Automation Publication 1783-UM007I-EN-P - December 2017
59
Get Started
Chapter 2
Table 21 - Fault/Program Action Fields
Field
Description
Port
Displays the port type and port number:
•
Fa—Fast Ethernet
•
Gi—Gigabit Ethernet
•
Te—10 Gigabit Ethernet
Program Mode
Choose what happens at the port when the controller transitions to Program mode:
•
Hold Last State—The port maintains the current state.
•
Disable—The port is disabled.
•
Enable—The port is enabled.
The default is Hold Last Sate.
Connection Fault
Choose what happens at the port when communication is lost between the controller and the switch:
•
Hold Last State—The port maintains the current state.
•
Disable—The port is disabled.
•
Enable—The port is enabled.
The default is Hold Last Sate.