Configure Switch Features
Chapter 3
Global Alarms
From the Configure menu, choose Alarm Settings and click the Global tab.
Table 26 - Global Tab Fields
Field
Description
FCS Hysteresis (1-10)
The frame check sequence (FCS) error hysteresis threshold determines when an alarm condition is cleared. This value is expressed as a percentage
of fluctuation from the FCS bit error rate. The default global setting is 10 percent.
You can adjust the percentage to help prevent toggling the alarm condition when the FCS bit error rate fluctuates near the configured bit error
rate. Valid percentages for global settings are 1…10. This setting can also be configured on an individual port by clicking the Port tab.
Alarm Name
These types of alarms can be enabled or disabled:
•
Dual Power Supply—The switch monitors DC power supply levels. If the system is configured to operate in a dual power mode, an alarm is
triggered if a power supply fails or is missing. The alarm is automatically cleared when the power supplies are present or working. You can
configure the power supply alarm to be connected to the hardware relays.
•
Temperature-Primary—These alarms are triggered when the system temperature is higher or lower than the configured thresholds. By
default, the primary temperature alarm is associated with the major relay.
•
Temperature-Secondary—These alarms are triggered when the system temperature is higher or lower than the configured thresholds.
•
License-File-Corrupt—An alarm is triggered when the license file is corrupt.
•
Input-Alarm 1—An alarm is triggered based on an external input alarm.
•
Input-Alarm 2—An alarm is triggered based on an external input alarm.
DM Alarms
Alarm information appears on the dashboard of Device Manager.
SNMP Trap
Alarm traps are sent to an SNMP server, if SNMP is enabled on the Configure > Security > SNMP page.
HW Relay
If the alarm relay is triggered, the switch sends a fault signal to a connected external alarm device, such as a bell, light, or other signaling device.
Syslog
Alarm traps are recorded in the syslog. You can view the syslog on the Monitor > Syslog page.
Thresholds (MAX) in
°C
The maximum temperature threshold for the corresponding Temperature-Primary or Temperature-Secondary alarm, if enabled.
Thresholds (MIN) in
°C
The minimum temperature threshold for the corresponding Temperature-Primary or Temperature-Secondary alarm, if enabled.
Summary of Contents for armorstratix 5700
Page 10: ...10 Rockwell Automation Publication 1783 UM007I EN P December 2017 Table of Contents Notes ...
Page 12: ...12 Rockwell Automation Publication 1783 UM007I EN P December 2017 Preface Notes ...
Page 72: ...72 Rockwell Automation Publication 1783 UM007I EN P December 2017 Chapter 2 Get Started Notes ...
Page 396: ...396 Rockwell Automation Publication 1783 UM007I EN P December 2017 Appendix A DataTypes Notes ...
Page 457: ......