230
Rockwell Automation Publication 1783-UM007I-EN-P - December 2017
Chapter 3
Configure Switch Features
Configure Port Thresholds via the Logix Designer Application
You can configure threshold limits for broadcast, unicast, and multicast traffic
for each active port. This feature is available only with Full firmware. The
number of packets being sent is compared against the threshold value. These
limits help to prevent a single device from sending too much traffic.
Figure 32 - Port Thresholds for Stratix 5400, Stratix 5410, Stratix 5700, and ArmorStratix 5700 Switches
Table 88 - Port Threshold Fields for Stratix 5400, Stratix 5410, Stratix 5700, and ArmorStratix 5700 Switches
Field
Description
Port
The port selected for configuration. The port number includes the port type (Fa for Fast Ethernet and Gi for Gigabit Ethernet),
and the specific port number.
EXAMPLE:
Gi1/1 is Gigabit Ethernet port 1.
Incoming Threshold Settings
Enable incoming thresholds and set the threshold values for the unicast, multicast, and broadcast traffic for each port.
Valid values for units:
•
Packets per second (pps)
•
Percentage of total bandwidth (%)
•
Bits per second (bps)
Outgoing Threshold Settings
Enable outgoing thresholds and set the threshold values for the traffic for each port.
Units % = Percentage of total bandwidth
Summary of Contents for armorstratix 5700
Page 10: ...10 Rockwell Automation Publication 1783 UM007I EN P December 2017 Table of Contents Notes ...
Page 12: ...12 Rockwell Automation Publication 1783 UM007I EN P December 2017 Preface Notes ...
Page 72: ...72 Rockwell Automation Publication 1783 UM007I EN P December 2017 Chapter 2 Get Started Notes ...
Page 396: ...396 Rockwell Automation Publication 1783 UM007I EN P December 2017 Appendix A DataTypes Notes ...
Page 457: ......