Rockwell Automation Publication 1783-UM007I-EN-P - December 2017
35
Get Started
Chapter 2
Configure Network Settings
via Device Manager
You can apply one of the following setup modes to the switch after you run
Express Setup as described on
•
Express Setup—Enables the switch to operate as a managed switch with
a default configuration that supports industrial automation applications.
Express Setup is the default setup mode.
•
Plug-n-Play (PnP)—Enables the switch to operate as an unmanaged
switch without an IP address.
Configure PnP server settings to enable the switch to send a work
request to a PnP server for further device configuration. The PnP agent
is a software application on the switch. When the switch is powered on
for the first time, the PnP agent discovery process, which is embedded in
the switch, wakes up in the absence of the startup configuration file and
attempts to discover the address of the PnP server. The PnP agent uses
methods like DHCP, Domain Name System (DNS), and others to
acquire the IP address of the PnP server. Once a server is found and
connection established, the agent performs activities, such as
configuration, image, license, and file updates by communicating with
the server.
If an auto discovery mechanism is not available, you can use the PnP
configuration option from Express Setup to configure the initial switch
settings and PnP server information.
Apply the PnP Setup Mode
To apply the PnP setup mode to the switch, follow these steps.
1.
Access Device Manager as described on
.
If the Express Setup page does not appear, try the following:
•
Verify that your network adapter is set to accept a DHCP address
•
Enter the URL of a well-known website in your browser to be sure
that the browser is working correctly. Your browser then redirects to
Express Setup.
•
Verify that any proxy settings or popup blockers are disabled on your
browser.
•
Verify that any wireless interface is disabled on the computer.
2.
From the Select device initial setup mode pull-down menu, choose PnP.
3.
Complete the fields as described in
and click Submit.
Summary of Contents for armorstratix 5700
Page 10: ...10 Rockwell Automation Publication 1783 UM007I EN P December 2017 Table of Contents Notes ...
Page 12: ...12 Rockwell Automation Publication 1783 UM007I EN P December 2017 Preface Notes ...
Page 72: ...72 Rockwell Automation Publication 1783 UM007I EN P December 2017 Chapter 2 Get Started Notes ...
Page 396: ...396 Rockwell Automation Publication 1783 UM007I EN P December 2017 Appendix A DataTypes Notes ...
Page 457: ......