Trouble shooting 51
No Operation (Power is ON)
Check Point 2 : Check outside cause at Indoor and Outdoor (Voltage drop or Noise)
Check Point 1 : Check indoor and outdoor installation condition
Check Point 3 : Check Electrical Components at Indoor and Outdoor
Indoor Unit - Check the voltage between pins 1-3 of the connector (on the control PCB) for connection with the remote controller.
>> If it is DC12V, Remote Control is defective (Controller PCB is normal) >> Replace Remote Control
>> If it is DC 0V, Controller PCB is defective (Check Remote Control once agein) >> Replace Controller PCB
If some of Indoor unit does not operate, replace the Communication PCB of the non-operative Indoor Unit.
>> If the symptom does not change, replace Controller PCB of Indoor Unit.
If all of Indoor Units do not operate, check the connection between Main PCB and Communication PCB of Outdoor Unit (Main Unit).
>> If the symptom does not change, replace Communication PCB of Outdoor Unit (Main Unit).
(If it did not work, replace Main PCB.)
Turn off Power and check/correct followings.
Isn't Communication PCB of Indoor Unit removed?
Is there loose or removed communication line of Indoor Unit and Outdoor Unit?
Check Terminator (DIP-SW SET 5) is installed on Outdoor Main PCB.
Check loose or removed communication line between each Outdoor Unit.
Check loose Communication PCB of each Outdoor Unit.
OK
OK
OK
DC
Forecast of Cause :
1. Setting/Connection failure 2. Outside cause
3. Electrical Component defective
Indoor Unit - Check incorrect wiring between Indoor Unit - Remote Control, or terminals between Indoor Units.
-
Or, check if there is an open cable connection.
Check address setting (Are all the address of Indoor and Outdoor correct?)
Are these Indoor Unit, Outdoor Unit, and Remote Control suitable model numbers to connect?
>> If there is some abnormal condition, correct it by referring to Installation manual and Data & Technical Manual.
Instant drop -----Check if there is a large load electric apparatus in the same circuit.
Momentary power failure ----- Check if there is a defective contact or leak current in the power supply circuit.
Noise ----- Check if there is any equipment causing harmonic wave near electric line (Neon bulb or electric equipment that may cause
harmonic wave).
Check the complete insulation of grounding.
04-60
Summary of Contents for ARXB07LALH
Page 1: ...Small VRF system for light commercial and home use SERVICE MANUAL...
Page 2: ......
Page 6: ......
Page 7: ...1 TEST RUN...
Page 8: ......
Page 27: ...2 OUTDOOR UNIT OPERATION CONTROL...
Page 28: ......
Page 42: ......
Page 43: ...3 INDOOR UNIT OPERATION...
Page 44: ......
Page 63: ...4 TROUBLE SHOOTING...
Page 74: ......
Page 171: ...5 APPENDING DATA UNIT...
Page 172: ......
Page 174: ...05 02 5 2 WIRING DIAGRAM 5 2 1 Indoor Unit MODELS AUXB07 09 12 14 18 24LALH...
Page 175: ...05 03 MODELS AUXD18 24LALH AUXA30 36 45 54LALH...
Page 176: ...05 04 MODELS ARXB07 09 12 14 18LALH...
Page 177: ...05 05 MODEL ARXB24LATH MODELS ARXB30 36LATH...
Page 178: ...05 06 MODEL ARXB45LATH...
Page 179: ...05 07 MODEL ARXA24LATH MODELS ARXA30 36 45LATH...
Page 180: ...MODELS ARXC36 45LATH 05 08...
Page 181: ...05 09 MODELS ARXD07 09 12 14 18 24LATH...
Page 182: ...MODELS AB A12 14 18 24LBTH 05 10...
Page 183: ...05 11 MODELS AB A30 36 45 54LBTH...
Page 184: ...MODELS AS A07 09 12 14LACH 05 12...
Page 185: ...MODELS AS E07 09 12 14LACH 05 13...
Page 186: ...MODELS AS A18 24 30LACH 05 14...
Page 187: ...05 15 MODELS AJ A36 45 54LALH 5 2 2 Outdoor Unit...
Page 192: ......
Page 193: ...6 DISASSEMBLY PROCESS...
Page 194: ......