Trouble shooting 4
INDOOR UNIT Error Method:
Room Temperature Sensor Error
Indicate or Display:
Indoor Unit : Operation LED 4 times Flash, Timer LED 1 Times Flash,
Filter LED Continuous Flash.
Outdoor Unit : E.5 U.1
Error Code : 4 1
Detective Actuators:
Indoor Unit Controller PCB Circuit
Indoor Temperature Thermistor
Detective details:
When Indoor thermistor open or shortage is detected at power ON.
Forecast of Cause :
1. Connector defective connection 2. Thermistor defective 3. Controller PCB defective
Check Point 2 : Remove connector and check Thermistor resistance value
Thermistor Characteristics (Rough value)
If Thermistor is either open or shorted, replace it and reset the power.
Check Point 1 : Check connection of Connector
Check if connector is loose or removed
Check erroneous connection
Check if thermistor cable is open
>>Reset Power when reinstalling due to removed connector or incorrect wiring.
6.5
35
8.0
30
10.0
12.5
15.8
20.1
25.2
33.6
Resistance Value ( )
25
20
15
10
5
0
Temperature (°C)
3.5
4.3
5.3
Resistance Value ( )
50
45
40
Temperature (°C)
OK
OK
Check Point 3 : Check voltage of Controller PCB (DC5.0V)
Make sure circuit diagram of each indoor unit and check terminal voltage at Thermistor (DC5.0V)
Small size Wall mount Schematic Diagram(Direct soldering to PCB)
If the voltage does not appear, replace Controller PCB and set up the original address.
H/E Inlet Thermistor
(CN20 Wire:Black)
H/E Outlet Thermistor
(CN20 Wire:Gray)
Room Temp. Thermistor
(CN19 Wire:Black)
Room Temp. Thermistor
(CN10 Wire:Black)
H/E Intlet Thermistor
(CN12 Wire:Black)
H/E Outlet Thermistor
(CN11 Wire:Gray)
DC
Cassette Schematic Diagram (Connector connection)
Wall mount Schematic Diagram (Connector connection)
H/E Outlet Thermistor
(CN9 Wire:Gray)
H/E Inlet Thermistor
(CN9 Wire:Black)
Room Temp. Thermistor
(CN8 Wire:Black)
H/E Outlet Thermistor
(CN17Wire:Gray)
H/E Inlet Thermistor
(CN17 Wire:Black)
Room Temp. Thermistor
(CN16 Wire:Black)
04-14
Duct Schematic Diagram (Connector connection)
Summary of Contents for ARXB07LALH
Page 1: ...Small VRF system for light commercial and home use SERVICE MANUAL...
Page 2: ......
Page 6: ......
Page 7: ...1 TEST RUN...
Page 8: ......
Page 27: ...2 OUTDOOR UNIT OPERATION CONTROL...
Page 28: ......
Page 42: ......
Page 43: ...3 INDOOR UNIT OPERATION...
Page 44: ......
Page 63: ...4 TROUBLE SHOOTING...
Page 74: ......
Page 171: ...5 APPENDING DATA UNIT...
Page 172: ......
Page 174: ...05 02 5 2 WIRING DIAGRAM 5 2 1 Indoor Unit MODELS AUXB07 09 12 14 18 24LALH...
Page 175: ...05 03 MODELS AUXD18 24LALH AUXA30 36 45 54LALH...
Page 176: ...05 04 MODELS ARXB07 09 12 14 18LALH...
Page 177: ...05 05 MODEL ARXB24LATH MODELS ARXB30 36LATH...
Page 178: ...05 06 MODEL ARXB45LATH...
Page 179: ...05 07 MODEL ARXA24LATH MODELS ARXA30 36 45LATH...
Page 180: ...MODELS ARXC36 45LATH 05 08...
Page 181: ...05 09 MODELS ARXD07 09 12 14 18 24LATH...
Page 182: ...MODELS AB A12 14 18 24LBTH 05 10...
Page 183: ...05 11 MODELS AB A30 36 45 54LBTH...
Page 184: ...MODELS AS A07 09 12 14LACH 05 12...
Page 185: ...MODELS AS E07 09 12 14LACH 05 13...
Page 186: ...MODELS AS A18 24 30LACH 05 14...
Page 187: ...05 15 MODELS AJ A36 45 54LALH 5 2 2 Outdoor Unit...
Page 192: ......
Page 193: ...6 DISASSEMBLY PROCESS...
Page 194: ......