01-18
1-5 Field Setting / Function Setting for Indoor unit
Setting Mode
ITEM
CODE No.
Setting Function
Default
Indoor unit field setting
Address
setting by
remote controller
01
Indoor unit address
00~63
00~63
00
02
Refrigerant circuit address
00~99
00~99
00
Filter
11
Filter indicator Interval
00
Default
01
Longer
02
Shorter
13
Filter sign display
00
Enable
01
Disable
02
Display only on central remote control
Airflow
20
Ceiling airflow
00
Default
(Cassette type only)
01
High ceiling
23
Vertical airflow direction
00
Default
01
Raise
24
Horizontal swing airflow direction
00
Default
01
Left half
02
Right half
Correction
30
Cool air temperature trigger
00
Default (0
°C)
01
Temperature overshoot setting (+2
°C)
02
Temperature undershoot setting (-2
°C)
31
Heat air temperature trigger
00
Default (0
°C)
01
Temperature undershoot setting (-6
°C)
02
Temperature slightly undershoot setting (-4
°C)
03
Temperature overshoot setting (+4
°C)
Change of
40
Auto restart
00
Enable
01
Disable
43
Cool air prevention
00
Enable
01
Disable (Ventilation mode)
46
External control
00
Start / Stop
01
Emergency stop
47
Error report target
00
All
01
Display only for central remote control
ITEM
CODE No.
Function 1
Classification
26
32
Model name
Range of static pressure
ARXD07LATH
0 to 90 Pa
ARXD09LATH
ARXD12LATH
ARXD14LATH
ARXD18LATH
ARXD24LATH
0 to 50 Pa
00
01
02
03
04
05
06
07
08
09
31
0 Pa
10 Pa
20 Pa
30 Pa
40 Pa
50 Pa
60 Pa
70 Pa
80 Pa
90 Pa
25 Pa
Static Pressure setting
- Slim Duct Only -
The Range of static pressure is
different from one model to other.
Temperature correction in Auto
00
01
Disable
Enable (Nonfunctional on J2 Series)
Summary of Contents for ARXB07LALH
Page 1: ...Small VRF system for light commercial and home use SERVICE MANUAL...
Page 2: ......
Page 6: ......
Page 7: ...1 TEST RUN...
Page 8: ......
Page 27: ...2 OUTDOOR UNIT OPERATION CONTROL...
Page 28: ......
Page 42: ......
Page 43: ...3 INDOOR UNIT OPERATION...
Page 44: ......
Page 63: ...4 TROUBLE SHOOTING...
Page 74: ......
Page 171: ...5 APPENDING DATA UNIT...
Page 172: ......
Page 174: ...05 02 5 2 WIRING DIAGRAM 5 2 1 Indoor Unit MODELS AUXB07 09 12 14 18 24LALH...
Page 175: ...05 03 MODELS AUXD18 24LALH AUXA30 36 45 54LALH...
Page 176: ...05 04 MODELS ARXB07 09 12 14 18LALH...
Page 177: ...05 05 MODEL ARXB24LATH MODELS ARXB30 36LATH...
Page 178: ...05 06 MODEL ARXB45LATH...
Page 179: ...05 07 MODEL ARXA24LATH MODELS ARXA30 36 45LATH...
Page 180: ...MODELS ARXC36 45LATH 05 08...
Page 181: ...05 09 MODELS ARXD07 09 12 14 18 24LATH...
Page 182: ...MODELS AB A12 14 18 24LBTH 05 10...
Page 183: ...05 11 MODELS AB A30 36 45 54LBTH...
Page 184: ...MODELS AS A07 09 12 14LACH 05 12...
Page 185: ...MODELS AS E07 09 12 14LACH 05 13...
Page 186: ...MODELS AS A18 24 30LACH 05 14...
Page 187: ...05 15 MODELS AJ A36 45 54LALH 5 2 2 Outdoor Unit...
Page 192: ......
Page 193: ...6 DISASSEMBLY PROCESS...
Page 194: ......