3-2-3 "COOL" Position
An example for COOLING TEMPERATURE CONTROL time chart (Manual setting)
When using the cooling mode, set the temperature to a value lower than the current room temperature
, otherwise
the indoor unit will not start the cooling operation and only the fan will rotate.
• Indoor fan
Ts
• Opening of
EEV
100%
0%
• Refrigerant
flow
ON
OFF
ON
OFF
• Temperature
Ts + 0.5 C
T
R
3Min.
Ts : Corrected setting temperature
T
R
: Corrected room temperature
: The thres hold temperature of start of refrigrant flow
: The thres hold temperature of stop of refrigrant flow
Ts - 0.5 C
Ts + 0.5 C
Ts - 0.5 C
Ts + 0.5 C
Ts - 0.5 C
: The thres hold temperature of start of refrigrant flow
: The thres hold temperature of stop of refrigrant flow
Ts + 0.5 C
Ts - 0.5 C
3-2-4 "HEAT" Position
(1) When using the heating mode, set the temperature to a value higher than the current room temperature
, otherwise
the indoor unit will not start the heating operation.
(3)
An example for HEATING TEMPERATURE CONTROL time chart (Manual setting)
During defrosting, the OPERATION indicator lamp flashes 6 sec. ON and 2 sec. OFF, and repeat. The heating operation
will be temporarily interrupted.
• Indoor fan
Ts
• Opening of
EEV
100%
0%
• Refrigerant
flow
ON
OFF
ON
OFF
• Temperature
T
R
4Min. 1Min.
4Min. 1Min.
4Min. 1Min.
Ts : Corrected setting temperature
T
R
: Corrected room temperature
: Duration of cold air prevention
(2) After the start of heating operation, the fan of indoor unit will not rotate until the heater exchange is warmed up to
blow out warm air.
Summary of Contents for ARXB07LALH
Page 1: ...Small VRF system for light commercial and home use SERVICE MANUAL...
Page 2: ......
Page 6: ......
Page 7: ...1 TEST RUN...
Page 8: ......
Page 27: ...2 OUTDOOR UNIT OPERATION CONTROL...
Page 28: ......
Page 42: ......
Page 43: ...3 INDOOR UNIT OPERATION...
Page 44: ......
Page 63: ...4 TROUBLE SHOOTING...
Page 74: ......
Page 171: ...5 APPENDING DATA UNIT...
Page 172: ......
Page 174: ...05 02 5 2 WIRING DIAGRAM 5 2 1 Indoor Unit MODELS AUXB07 09 12 14 18 24LALH...
Page 175: ...05 03 MODELS AUXD18 24LALH AUXA30 36 45 54LALH...
Page 176: ...05 04 MODELS ARXB07 09 12 14 18LALH...
Page 177: ...05 05 MODEL ARXB24LATH MODELS ARXB30 36LATH...
Page 178: ...05 06 MODEL ARXB45LATH...
Page 179: ...05 07 MODEL ARXA24LATH MODELS ARXA30 36 45LATH...
Page 180: ...MODELS ARXC36 45LATH 05 08...
Page 181: ...05 09 MODELS ARXD07 09 12 14 18 24LATH...
Page 182: ...MODELS AB A12 14 18 24LBTH 05 10...
Page 183: ...05 11 MODELS AB A30 36 45 54LBTH...
Page 184: ...MODELS AS A07 09 12 14LACH 05 12...
Page 185: ...MODELS AS E07 09 12 14LACH 05 13...
Page 186: ...MODELS AS A18 24 30LACH 05 14...
Page 187: ...05 15 MODELS AJ A36 45 54LALH 5 2 2 Outdoor Unit...
Page 192: ......
Page 193: ...6 DISASSEMBLY PROCESS...
Page 194: ......