01-02
[Note] Perform in the power OFF state.
Execution 2/2
Set according to the length of the connection piping.
Set to "Standard (40 to 65m)" at the factory.
Set using the push button SW on the outdoor unit main PCB.
< Refer to the Page 01-16 Setting mode F2-00 >
Set the pipe length to be the nearest indoor unit from the outdoor unit
Set the refrigerant circuit address and indoor unit address.
Can be set by rotary SW on the indoor unit PCB ( Main PCB or Switch
PCB) or from a remote controller or from a push button SW on the
outdoor unit Main PCB < Automatic address setting,
Refer to the Page 01-07 Setting mode F3-11>
Initial setting
Gas leak test
Use an R410A dedicated leak tester to check for gas leaks.
1
2
3
Confirm the additional refrigerant amount with the installation
manual, etc.
Always take the R410A refrigerant from the cylinder liquid phase
and charge it using the gas phase.
(Do not lay a cylinder with siphon pipe on its side.)
Use an R410A dedicated gauge manifold and charging hose.
Charge refrigerant using the liquid pipe.
When the defined amount of refrigerant cannot charge using the
liquid pipe, charge refrigerant using the gas pipe while opearing
the cooling test run.
Charge refrigerant bit by bit with cautious operation of valve
for the liquid refrigerant back prevention.
If taken from the air phase, since the
composition of the refrigerant which is
charged will change, low performance
and abnormal stop will occur easily.
Prevent erroneous sealing in of
refrigerant.
A leak tester for other than R410A
cannot detect leaks.
Set the refrigerant circuit address.
ROTARY SW: REF ADX10, X1
4
Turnover & explanation of operation
Address setting for Indoor unit
Test run & adjustment
Piping length setting
Addition refrigerant charging
5
Indoor unit connection check
[Note] Perform setting by push button SW on the outdoor unit Main PCB in the power ON state
after all indoor units have stopped operation.
When setting the address of Signal amplifier, please refer to the
installation manual of the signal amplifier.
The address setting can be set by automatically from 1 outdoor unit
on the network. < Refer to the Page 01-06 Setting mode F3-10 >
Address setting for Signal Amp
- When using signal Amps -
[Note] Manual setting: Set the rotary SW on the PCB in the power OFF state.
Automatic address setting:
Perform setting by push button SW on the outdoor unit Main PCB in the
power ON state after all indoor units have stopped operation.
[Note] Perform in the power ON state after all indoor units have stopped operation
[Note] Manual setting: Set the rotary SW on the PCB in the power OFF state.
Automatic address setting:
Perform setting by push button SW on the outdoor unit Main PCB in the
power ON state after all indoor units have stopped operation.
Dual address setting No. is not
allowed in one network.
When the setting is not same as the
real piping length, the system may
not work correctly.
Dual address setting No. is not
allowed in one network.
Dual address setting No. is not
allowed in one network.
Normal operation will not be possible
without performing the indoor unit
connection check.
Before starting the system, check on the number of indoor units and
the total capacity.
< Refer to the Page 01-08 Setting mode F3-12 >
Execution procedure and precautions
Reason
1
2 Confirm the DIP SW setting
SET 1: Factory setting, SET 2 : All OFF, SET 3 : All OFF,
SET 4: Factory setting
If the DIP SW setting is wrong, the sys-
tem may not work correctly
3 Confirm the Terminal resister setting
SET 5-4 OFF: Disable, ON: Enable
If the Terminal resister setting is wrong,
the system may detect transmission
error
If the pipe length is set as the farthest
indoor unit, the nearest operating
indoor unit may be stopped the
operation by the icing up protection
as by over cooling.
Summary of Contents for ARXB07LALH
Page 1: ...Small VRF system for light commercial and home use SERVICE MANUAL...
Page 2: ......
Page 6: ......
Page 7: ...1 TEST RUN...
Page 8: ......
Page 27: ...2 OUTDOOR UNIT OPERATION CONTROL...
Page 28: ......
Page 42: ......
Page 43: ...3 INDOOR UNIT OPERATION...
Page 44: ......
Page 63: ...4 TROUBLE SHOOTING...
Page 74: ......
Page 171: ...5 APPENDING DATA UNIT...
Page 172: ......
Page 174: ...05 02 5 2 WIRING DIAGRAM 5 2 1 Indoor Unit MODELS AUXB07 09 12 14 18 24LALH...
Page 175: ...05 03 MODELS AUXD18 24LALH AUXA30 36 45 54LALH...
Page 176: ...05 04 MODELS ARXB07 09 12 14 18LALH...
Page 177: ...05 05 MODEL ARXB24LATH MODELS ARXB30 36LATH...
Page 178: ...05 06 MODEL ARXB45LATH...
Page 179: ...05 07 MODEL ARXA24LATH MODELS ARXA30 36 45LATH...
Page 180: ...MODELS ARXC36 45LATH 05 08...
Page 181: ...05 09 MODELS ARXD07 09 12 14 18 24LATH...
Page 182: ...MODELS AB A12 14 18 24LBTH 05 10...
Page 183: ...05 11 MODELS AB A30 36 45 54LBTH...
Page 184: ...MODELS AS A07 09 12 14LACH 05 12...
Page 185: ...MODELS AS E07 09 12 14LACH 05 13...
Page 186: ...MODELS AS A18 24 30LACH 05 14...
Page 187: ...05 15 MODELS AJ A36 45 54LALH 5 2 2 Outdoor Unit...
Page 192: ......
Page 193: ...6 DISASSEMBLY PROCESS...
Page 194: ......