Trouble shooting 53
Abnormal Noise
Abnormal noise is coming from Indoor Unit
(Check and correct followings)
Diagnosis method when Abnormal Noise is occurred
Abnormal noise is coming from Outdoor Unit
(Check and correct followings)
Trouble shooting 54
Water Leaking
Diagnosis method when water leak occurs
Diagnosis method when water is spitting out
Attention!!
If water is leaking from the Indoor Unit that is not in
operation, there is a possibility of Indoor EEV is not
closed.
=> Check EEV (Refer to Service Parts Information)
Attention!!
If Refrigerant Noise is occurring, Check if the Indoor and
Outdoor Thermistor is wrongly installed. Check and
correct the thermistor.
OK
Is Fan broken or deformed?
Is the screw of Fan loose?
Is there any object which obstruct the Fan rotation?
Is Fan broken or deformed?
Is the screw of Fan loose?
Is there any object which obstruct the Fan rotation?
Check if vibration noise by loose bolt or contact noise of
piping is happening.
Is Compressor locked?
>> Check Compressor (Refer to Service Parts Information)
OK
OK
Is Main Unit installed in stable condition?
Is the installation of Air suction grille and front panel normal?
In case of Duct type : Is Static Pressure range normal?
(Refer to Data & Technical Manual)
Is Main Unit installed in stable condition?
Is Bell Mouth installed normally?
OK
Is Float Switch defective?
>> Check Float Switch (Refer to Trouble Shooting)
Is Fan rotating?
>> Check Fan Motor (Refer to Service Parts Information)
Is Drain Hose connection loose?
Is there a trap in Drain Hose?
Is Drain Hose clogged?
Is Main Unit installed in stable condition?
Is Main Unit broken or deformed at the time of
transportation or maintenance?
OK
OK
OK
Check Gas Pressure and correct it if there was a gas leak.
Is the filter clogged?
OK
MPa MPa
Forecast of Cause :
1. Abnormal installation (Indoor/Outdoor) 2. Fan failure(Indoor/Outdoor)
3. EEV failure (Indoor) 4. Compressor failure (Outdoor)
Forecast of Cause :
1. Erroneous installation 2. Drain hose failure 3. Float Switch failure
04-62
Check the refrigerant additional charging amount.
When the refrigerant is not enough, add the refrigerant.
However, the total refrigerant amount is prevented from
more than 15.7kg.
Summary of Contents for ARXB07LALH
Page 1: ...Small VRF system for light commercial and home use SERVICE MANUAL...
Page 2: ......
Page 6: ......
Page 7: ...1 TEST RUN...
Page 8: ......
Page 27: ...2 OUTDOOR UNIT OPERATION CONTROL...
Page 28: ......
Page 42: ......
Page 43: ...3 INDOOR UNIT OPERATION...
Page 44: ......
Page 63: ...4 TROUBLE SHOOTING...
Page 74: ......
Page 171: ...5 APPENDING DATA UNIT...
Page 172: ......
Page 174: ...05 02 5 2 WIRING DIAGRAM 5 2 1 Indoor Unit MODELS AUXB07 09 12 14 18 24LALH...
Page 175: ...05 03 MODELS AUXD18 24LALH AUXA30 36 45 54LALH...
Page 176: ...05 04 MODELS ARXB07 09 12 14 18LALH...
Page 177: ...05 05 MODEL ARXB24LATH MODELS ARXB30 36LATH...
Page 178: ...05 06 MODEL ARXB45LATH...
Page 179: ...05 07 MODEL ARXA24LATH MODELS ARXA30 36 45LATH...
Page 180: ...MODELS ARXC36 45LATH 05 08...
Page 181: ...05 09 MODELS ARXD07 09 12 14 18 24LATH...
Page 182: ...MODELS AB A12 14 18 24LBTH 05 10...
Page 183: ...05 11 MODELS AB A30 36 45 54LBTH...
Page 184: ...MODELS AS A07 09 12 14LACH 05 12...
Page 185: ...MODELS AS E07 09 12 14LACH 05 13...
Page 186: ...MODELS AS A18 24 30LACH 05 14...
Page 187: ...05 15 MODELS AJ A36 45 54LALH 5 2 2 Outdoor Unit...
Page 192: ......
Page 193: ...6 DISASSEMBLY PROCESS...
Page 194: ......