Error Contents :
Communication Error
with Indoor Unit
Symptom :
Error Code display [ 1 6 ]
All the control items do not operate.
Details :
Condition of occurrence : The communication between Indoor unit and Network Convertor was not performed normally.
Release condition : When the communication with Indoor unit is resumed normally.
Cause 2 :
Defective or open connection of Remote Control cable between Network Convertor and Indoor Unit.
Cause 4 : Incorrect setting of main unit address of Indoor unit.
Check main unit address setting of Indoor unit.
Cause 5 : Incorrect setting of DIP-SW of Network Convertor. Mis-read of Indoor unit type and RC type.
Check DIP-SW103[1 to 8] of Network Convertor (Indoor unit type, RC type, number of Indoor units connected.)
Check Indoor unit type and RC type of all Indoor units connected to Network Convertor.
Cause 6 : Defective PCB of Indoor unit or Network Convertor.
Replace PCB of Controller PCB or Network Convertor.
Cause 3 : Power to Indoor unit is shut down.
Check the power to Indoor unit.
Cause 1 : External noise
After pressing SW104 of Network Convertor PCB for 5 seconds or turning on power.
Does error code display reappear?
It is not a defect of PCB. Remove the surrounding noise source.
Remove the surrounding noise source.
YES
OK
NO
OK
OK
OK
OK
Trouble shooting 73
After the following are checked, the power supply is reset.
Check connection cable wire between Network Convertor and Indoor unit.
Check connection between Control PCB and Terminal.
04-73
Summary of Contents for ARXB07LALH
Page 1: ...Small VRF system for light commercial and home use SERVICE MANUAL...
Page 2: ......
Page 6: ......
Page 7: ...1 TEST RUN...
Page 8: ......
Page 27: ...2 OUTDOOR UNIT OPERATION CONTROL...
Page 28: ......
Page 42: ......
Page 43: ...3 INDOOR UNIT OPERATION...
Page 44: ......
Page 63: ...4 TROUBLE SHOOTING...
Page 74: ......
Page 171: ...5 APPENDING DATA UNIT...
Page 172: ......
Page 174: ...05 02 5 2 WIRING DIAGRAM 5 2 1 Indoor Unit MODELS AUXB07 09 12 14 18 24LALH...
Page 175: ...05 03 MODELS AUXD18 24LALH AUXA30 36 45 54LALH...
Page 176: ...05 04 MODELS ARXB07 09 12 14 18LALH...
Page 177: ...05 05 MODEL ARXB24LATH MODELS ARXB30 36LATH...
Page 178: ...05 06 MODEL ARXB45LATH...
Page 179: ...05 07 MODEL ARXA24LATH MODELS ARXA30 36 45LATH...
Page 180: ...MODELS ARXC36 45LATH 05 08...
Page 181: ...05 09 MODELS ARXD07 09 12 14 18 24LATH...
Page 182: ...MODELS AB A12 14 18 24LBTH 05 10...
Page 183: ...05 11 MODELS AB A30 36 45 54LBTH...
Page 184: ...MODELS AS A07 09 12 14LACH 05 12...
Page 185: ...MODELS AS E07 09 12 14LACH 05 13...
Page 186: ...MODELS AS A18 24 30LACH 05 14...
Page 187: ...05 15 MODELS AJ A36 45 54LALH 5 2 2 Outdoor Unit...
Page 192: ......
Page 193: ...6 DISASSEMBLY PROCESS...
Page 194: ......