02-12
Protective Function Detect Parts
Operating Condition
Operation
Low Pressure
Protection 4
Low Pressure
Sensor
COOL HEAT
High Pressure
Protection Stop 1
High Pressure
Sensor
<Pattern starting condition>
High-pressure 4.00MPa
<Pattern reset condition>
5 minutes have elapsed and high-pressure 3.50MPa
Compressor stopped
<Pattern starting condition>
Pattern generated 3 times within 60 minutes.
<Pattern reset condition>
10 minutes have elapsed and high-pressure 3.50MPa
Pressure Switch
<Pattern starting condition>
Pressure SW operated (Operated by high-pressure 4.20MPa)
<Pattern reset condition>
5 minutes have elapsed and pressure SW operation reset
(Reset by high-pressure 3.2MPa)
Compressor stopped
High Pressure
Protection Stop 2
<Pattern starting condition>
Pattern generated 3 times within 60 minutes.
<Pattern reset condition>
10 minutes have elapsed and pressure SW operation reset
(Reset by high-pressure 3.2MPa)
Compressor stopped
Error display
<Starting conditions>
Low-pressure 0.20MPa
<Reset conditions>
5 minutes have elapsed and low-pressure 0.30MPa
SV2 ON
Low Pressure
Protection 1
Low Pressure
Sensor
<Starting conditions>
Low-pressure 0.10MPa
<Reset conditions>
3 minutes have elapsed and low-pressure 0.17MPa
SV2 ON
<Starting conditions>
3 minutes have elapsed and low-pressure 0.18MPa
<Reset conditions>
3 minutes have elapsed and low-pressure 0.22MPa
EEV of stopped indoor unit opened quickly
(450pls)
Abnormal Low
Pressure Protection
Control
Low Pressure
Sensor
<starting condition>
Low-pressure 0.16MPa
Compressor capacity lowered every 180 secs,
Low Pressure
Protection Stop
Low Pressure
Sensor
<Pattern starting condition>
Low-pressure 0.05MPa or low-pressure 0.10MPa continues for 10 mins
<Pattern reset condition>
3 minutes have elapsed and low-pressure 0.17MPa
<Pattern starting condition>
Pattern generated 5 times within 180 minutes.
<Pattern reset condition>
Error reset (push button SW) executed after power turned on again.
Compressor stopped
(permanent stop)
Error display
Low Pressure
Sensor
Low Pressure
Protection 2
<reset condition>
3 minutes have elapsed and
low-pressure 0.18MPa
Compressor stopped
DISPLAY
Compressor Temp
Protection Stop
Compressor
Temp
Thermistor
<Pattern starting condition>
Compressor temperature fixed value (110°C)
<Pattern reset condition>
3 minutes have elapsed and discharge temperature 80°C
Compressor stopped
Compressor stopped
(permanent stop)
Error display
<Pattern starting condition>
Pattern generated 2 times within 40 minutes
<Pattern reset condition>
Error reset (push button SW) executed after power turned on again
P2
EA41
EA31
EA42
P4
P3
EA51
when the Low-pressure becomes more than
0.17MPa, prohibit compressor capacity rise.
P2
Compressor stopped
Summary of Contents for ARXB07LALH
Page 1: ...Small VRF system for light commercial and home use SERVICE MANUAL...
Page 2: ......
Page 6: ......
Page 7: ...1 TEST RUN...
Page 8: ......
Page 27: ...2 OUTDOOR UNIT OPERATION CONTROL...
Page 28: ......
Page 42: ......
Page 43: ...3 INDOOR UNIT OPERATION...
Page 44: ......
Page 63: ...4 TROUBLE SHOOTING...
Page 74: ......
Page 171: ...5 APPENDING DATA UNIT...
Page 172: ......
Page 174: ...05 02 5 2 WIRING DIAGRAM 5 2 1 Indoor Unit MODELS AUXB07 09 12 14 18 24LALH...
Page 175: ...05 03 MODELS AUXD18 24LALH AUXA30 36 45 54LALH...
Page 176: ...05 04 MODELS ARXB07 09 12 14 18LALH...
Page 177: ...05 05 MODEL ARXB24LATH MODELS ARXB30 36LATH...
Page 178: ...05 06 MODEL ARXB45LATH...
Page 179: ...05 07 MODEL ARXA24LATH MODELS ARXA30 36 45LATH...
Page 180: ...MODELS ARXC36 45LATH 05 08...
Page 181: ...05 09 MODELS ARXD07 09 12 14 18 24LATH...
Page 182: ...MODELS AB A12 14 18 24LBTH 05 10...
Page 183: ...05 11 MODELS AB A30 36 45 54LBTH...
Page 184: ...MODELS AS A07 09 12 14LACH 05 12...
Page 185: ...MODELS AS E07 09 12 14LACH 05 13...
Page 186: ...MODELS AS A18 24 30LACH 05 14...
Page 187: ...05 15 MODELS AJ A36 45 54LALH 5 2 2 Outdoor Unit...
Page 192: ......
Page 193: ...6 DISASSEMBLY PROCESS...
Page 194: ......